The RAVV is a non-electric operator that thermostatically controls the flow of water through the VMT 2-way valve. The self regulation of temperature control through the RAVV and VMT assembly is primarily used for storage tanks, radiant heating or heat exchanger applications. Features: • Non-electric operation of the valve • 4.5 ft remote sensor bulb • Lockable temperature setting • Ideal for radiant heating applications

Ordering Information:

Accessories:

Code No.

Range

013U1251

104°F - 158°F (40°C - 70°C)

013U1252

80°F - 132°F (27°C - 56°C)

013U1255

50°F - 100°F (10°C - 38°C)

Code No. 017-4370

Valve Bodies:

Code No.

065F1242

4’-6” (1.4 m)

248°F (120°C)

1/2” Brass Sensor Well, length 4.5”

Style

Connection VMT valve 1/2” Female solder unions

065F8960 065F0104

Maximum Sensor Temperature

Description

065F0102

065F8961

Capillary tube length

2-way

VMT valve 3/4” Female solder unions VMT valve 1” Male NPT unions

VDFCC122 © Danfoss 05/09

Cv 1.8 3.3 2.7 5.9 9.4

1

Data sheet

RAVV Thermostatic Operator

System Layout:

Hot Water Storage Tank

Plate Heat Exchanger

Floor Heating System

RAVV Scale Settings:

2

1 in (mm)

2 in (mm)

3 in (mm)

4 in (mm)

5 in (mm)

50° - 100°F (10° - 38°C)

53 (12)

64 (18)

75 (24)

86 (30)

96 (35)

80° - 132°F (27°C - 56°C)

86 (30)

97 (36)

108 (18)

119 (48)

129 (53)

104° - 158°F (40° - 70°C)

108 (42)

119 (48)

129 (18)

140 (60)

151 (66)

Scale Setting °F (°C)

VDFCC122 © Danfoss 05/09

Data sheet

RAVV Thermostatic Operator

Sensor Orientation:

The sensor must be installed in a position from horizontal to vertically down. When mounting the sensor in a medium, the sensor should be placed within a sensor pocket (017-4370). The flow temperature must be a minimum 37°F (15°C) higher than the set closing temperature.

Design:

1. Setting knob 2. Setting spring 3. Bellows 4. Gland 5. Bottom screw 6. Valve body 7. Valve cone 8. Remote sensor

Materials in contact with system fluid Valve body

Ms58, nickel plated

Valve cone

NBR rubber

Pressure pin

CrMo steel

O-ring

EPDM rubber

Sensor

Cu, nickel plated

VDFCC122 © Danfoss 05/09

3

Data sheet

RAVV Thermostatic Operator

Dimensions: øC

D

H

A L1 øB

L2

RAVV and VMT valve assembly, in (mm)

Typical Specifications:

Size

L1 in (mm)

L2 in (mm)

H in (mm)

1/2”

2.6 (66)

3.54 (90)

3.66 (93)

3/4”

2.91 (74)

3.98 (101)

3.66 (93)

1”

3.54 (90)

4.72 (120)

4.17 (106)

The operator shall be a self contained thermostatic controller with a remote sensor. The available remote sensor shall have a 4.5’ capillary tube capable of being inserted within a sensor well or pipe mounted. The thermostatic operator shall be adaptable to a Danfoss 2-way

A in (mm)

B in (mm)

C in (mm)

D in (mm)

3.94 (100)

0.37 (9.4)

2.17 (55)

3.07 (78)

VMT style of valve. The temperature range of the operator shall have the ability to control temperatures from 50° - 158°F (10° - 70°C). The setting of the operator shall be done with the dial which is mounted to the valve.

Danfoss can accept no responsibility for possible errors in printed materials and reserves the right to alter its products without notice. All trademarks in this material are property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.