››ENR ››Monitoring Relays ››Level Monitoring Relays ››DIN Rail Mount 22,5 mm ››Regulation of 1 or 2 levels (min / max) ››Monitoring filling (UP) or emptying (DOWN) selec-

ted by a switch on the front panel ››Probes supplied with AC current ››Time delay preventing wave effect adjustable from 0.1 to 5s (ENRM) ››Sensitivity adjustable on front panel from 250 ö to 1 M ö (ENRM) ››Sensitivity adjustable on front panel from 5 Kö to 100 k ö (ENR)

Specifications Characteristics

Voltages

Code

Monitoring filling (UP) Monitoring emptying (DOWN)

24 →240 V AC/DC

84870200

Characteristics Operating range

24 →240 V AC/DC

Operating range

20,4 →264 V AC/DC

Maximum power consumption

AC 5 VA, DC 1,5 W

Adjustable sensitivity

5 KOhm(s) →100 KOhm(s)

Measurement accuracy (at maximum sensitivity)

± 30 %

Electrode voltage (max)

12 V

Electrode current (maximum)

1 mA

Maximum cable capacity

10 nF

Response time high level

300 ms

Response time low level

500 ms

Output relay (according to AC1 resistive load)

1 changeover relay 8 A AC max.

Isolation of contacts and electrodes from power supply

2,5 kV AC

Operating temperature range (°C)

-20 →+50 °C

Storage temperature range (°C)

-40 →+70 °C

Weight (g)

91

I Monitoring Relays

I 02

I www.crouzet-control.com

Dimensions ENR 68 22.5

23.2

5.5

2.6

90

67.5 45

44

Curves

Connections U + A1

11

C Min Max

R

U

_

A2

12

14 A1

A2

NC

Min

Max

C

Serial number & date code U A1

C

Min Max 11 R

A2

12

: 24-240VAC 50-60Hz 5VA U 24-240VDC 1,5W : 8A/250V IEC60255-1

US LISTED 44UF

IND.CONT. EQ.

00000 PP-YYYY-Www

14

Un

C

Up

Down

30 20

70 80 90

10 5

Max

100

KΩ

Min

Sensitivity

R

ENR 84 870 200

ENR

Down R Up

Un R

Made in Indonesia

ENR Use copper conductors only TORQUE: 0,6...1N.m 5.3...8.8lbf.in

6mm

6mm

2 2x 0,5...2,5mm 20...14AWG

2 2x 0,5...1,5mm 20...16AWG

12

11

14