Installation of Environmental Sensors - Panduit

NET-ACCESS SENSOR MOUNTING AND CABLE ROUTING TO NETWORKED W / ENVIRONMENTAL OR SWITCHED POU INSTRUCTIONS CM539 © Panduit Corp. 2011

Installation of Environmental Sensors Recommended sensor placement includes (3) temperature / humidity / airflow / dewpoint sensors and (1) Temperature Sensor. • Install (3) PVQ-ESTAFHD-12 to the front door using (6) 5/8” plastic retainers, (6) #6-32 screws, (6) #6-32 nuts (or cable ties for PVQ-EST-12) , and route cable on door using small clips (ACC19-AV-M300). • Install (1) temperature sensor in the rear of cabinet, route cable using cable ties. Note: For CS Cabinets slit the seal in the air dam and route cable thru the slit.

Note: attach sensors to door, then route cable to Networked POU.

5/8” Plastic Retainers

Rear

Front

(3) PVQ-ESTAFHD-12 Note: Sensor must be oriented as shown, with open slots facing the front of the door for proper air flow readings. APPLICATION 1

Cable tie (3) PVQ-EST-12 APPLICATION 2

PVQ-EST-12 Note: Route / secure to inside of Top Cap.

Note: Before securing sensors, rotate door to the maximum open position to ensure enough slack for proper door operation.

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 1 of 8

INSTRUCTIONS CM539

Routing Sensor cable to Networked with Environmental or Switched POU •

Route cable to Networked with Environmental or Switched POU, as shown below after mounting CNFBB and WMPFSE. (1) Temperature Sensor Note: Manage sensor cable slack on cabinet post or on rear of the POU, using adhesive back clips. For 48” Deep Cabinets manage slack on the inside of Side Panel extension using adhesive mount clips.

Front

Rear

CNFBB Bracket for mounting cable manager. WMPFSE Note: Manage slack in cable manager.

POU

Route sensor cable thru the cable manager to the Networked with Enviromental or Switched POU. Manage slack in cable manager.

REAR DOORS REMOVED FOR CLARITY

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 2 of 8

INSTRUCTIONS CM539

Installation of Front Door Sensors • • • •

For CS Cabinet: Install (1) door sensor with (1) air dam bracket, (2) #6-32 nuts, and (2) #6-32 screws. For CN Cabinet: Install (1) door sensor with (1) front door bracket, (2) #6-32 nuts, and (2) #6-32 screws. Install (1) sensor with (1) double sided tape. Note: Ensure proper alignment with mating frame sensor before permanently affixing sensor with double sided tape on door.

Air Dam Bracket

(1) Door Sensor

Note: For CS Installationremove air dam screws, place bracket and reinstall screws to attach bracket to cabinet.

Front of cabinet

1/8” Note: For proper readings, sensors must be aligned as shown.

CS INSTALLATION (2) #6-32 Screws (2) #6-32 Nuts (2) #12-24 Screws Note: For CN installtion use this bracket.

3.6”

(1) Door Sensor Note: Apply double sided tape to sensor and install as shown. Center sensor on door. (2) #6-32 Screws (2) #6-32 Nuts

CN INSTALLATION

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 3 of 8

INSTRUCTIONS CM539

Front Door Sensor Cable Routing •

Route front door sensor cable to the Networked with Environmental or Switched POU in the rear of the cabinet, as shown below. Route sensor cable thru the cable manager to the Networked with Environmental or Switched POU. Manage slack in cable manager.

POU

Front Rear

Front Door Sensor Cable Note: For CS Application route through clearance hole in the equipment rail and attach to post with push mount cable ties.

Front Door Sensor Note:For CS Application route through bolt down hole and underneath the air dam.

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 4 of 8

INSTRUCTIONS CM539

Installation of Rear Door Sensors • •

For 41” Deep: Install (2) rear door sensors with (1) 41” rear bracket, (1) double sided tape, (2) #6-32 nuts, and (2) #12-24 screw. For 48” Deep: Install (2) rear door sensors with (1) 48” rear bracket, (1) double sided tape, (2) #6-32 nuts, and (2) #12-24 screw.

Note: For proper readings, sensors must be aligned as shown.

1/8”

(2) #12-24 Screw

(1) Door Sensor

41” Deep Rear of Cabinet

41” Rear Bracket (2) #6-32 Nuts (1) #5/16-18 Nut

48” Rear Bracket

(1) Door Sensor Note: Install with double sided tape

48” Deep Rear of Cabinet

(1) Door Sensor

(1) Door Sensor Note: Install with double sided tape

(2) #6-32 Nuts

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 5 of 8

INSTRUCTIONS CM539

Rear Door Sensor Cable Routing •

Route rear door sensor cable to Networked with Environmental or Switched POU, as shown below.

POU

Rear

Front

Rear Door Sensor Cable Note: Attach cable to outside of post using adhesive back clips. Rear Door Sensor

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 6 of 8

INSTRUCTIONS CM539

Installation of Remote Display / Cable Routing • •

Install remote display to rear door with (2) sheet metal screws, (2) #6-32 nuts, (2) #6-32 screws, and (2) #6 washers. Route remote display cable to Networked with Environmental or Switched POU. Note: Remote Display can be intalled facing into the cabinet, or facing out of the cabinet. Remote Display Note: Additional Remote Displays can be added at any position on the perforation of the door.

POU

(2) #6-32 Screws

Front

Rear

(2) #6 Washers

Remote Display Cable Note: Use Adhesive back Clips to manage slack behind POU.

(2) #6-32 Nuts

(2) Sheet Metal Screws

For Technical Support: www.panduit.com/resources/install_maintain.asp Page 7 of 8

INSTRUCTIONS CM539

Installation of Remote Display in 48” Deep Applications •

Install Remote Display with (2) #12-24 screws, (2) sheet metal screws and (1) remote display bracket to POU Bracket in the rear of the cabinet.

CVPDUB48 (2) #12-24 Screws (2) Sheet Metal Screws

Remote Display

For Instructions in Local Languages and Technical Support: www.panduit.com/resources/install_maintain.asp

www.panduit.com Page 8 of 8