The Boiler Control 270 is designed to operate a single modulating boiler using Outdoor Temperature Reset. It can be used in applications ranging from baseboard or radiant heating systems, to combination radiant and DHW systems. This control regulates a single heating water temperature through Outdoor Temperature Reset and/or setpoint/DHW control. It is capable of controlling a single modulating boiler, as well as the system pump.
Front View
Side View Boiler Demand DHW Demand Modulation DHW Priority Override
Advanced Installer
Mounting Base
1/2” (13 mm) 7/8” (23 mm)
CL
Off Exercise
Test off red red
not testing testing testing paused
For maximum heat press & hold Test button for 3 seconds.
Menu
Item Made in Canada by tekmar Control Systems Ltd. tektra 969-03 Power Relays Demands
Boiler Control 270
One Modulating Boiler & DHW
Meets Class B: Canadian ICES FCC Part 15
115 V ±10% 50/60 Hz 600 VA 230 V (ac) 5 A 1/3 hp, pilot duty 240 VA 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Date Code
6–5/8” (170 mm)
4 5 6 7 8 Prim Power P1 L N
DHW Pmp/Vlv
9 0
2 3 4 5 6 7 8
Boiler Pmp P2
Mod V(dc) Com UnO Boil Out Com Indr + -Sw
H2039A
Do not apply power
2 3 Boil Com DHW Dem Dem Dem
1/2” (14 mm) 1–7/8” (49 mm) 7–5/8” (193 mm)
2–7/8” (72 mm)
Ø 3/16” (5 mm)
1/2” Knock-out (x 5 back) (x 5 bottom)
Specifications------------------------------------------------------ Energy Saving Features-----------Boiler Control 270 One Modulating Boiler & DHW Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Relay Modulation output Demands Sensors –Included –Optional Warranty
D270, A270, D001, D070 Microprocessor control. This is not a safety (limit) control 3.3 lb. (1500 g) 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm) Blue PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Noncondensing, Altitude