RFI #009 Turner Construction - Portland 601 Main Street Suite 206 Vancouver, Washington

Project: 160315 - NIKE TECH - NW Campus One Bowerman Drive Beaverton, Oregon 97005

EG1 - Non-Structural Framing Questions TO:

Camilla Cok (Hennebery Eddy Architects)

FROM:

Georg Gold (Turner Construction Company)

DATE INITIATED:

04/19/ 2016

STATUS:

Open

LOCATION:

DUE DATE:

04/21/2016

COST CODE:

REFERENCE:

COST IMPACT:

SCHEDULE IMPACT:

DRAWING NUMBER: A201.A, S201.A, S401

SPEC SECTION:

09 22 19 - Non - Structural Metal Framing

LINKED DRAWINGS: EN-S301.A, EN-S401 RECEIVED FROM:

Jorge Hernandez (Interior / Exterior Specialist)

COPIES TO: Kate Bricker (Turner Construction - Portland), Camilla Cok (Hennebery Eddy Architects), Jeshua Dejongh (Hennebery Eddy Architects), Vincent Figini (Turner Construction - Portland), Nathan Pool (Interior / Exterior Specialist), Ted Wiberg (Interior / Exterior Specialist)

Question from Georg Gold (Turner Construction Company) at 11:47 PM on 04/19/2016 Question #1: On detail 5/S401 full height studs are shown to be attached to roof purlin with (3) #10 screws. Would it be acceptable to use (3) 1 ¼” Tico Nails instead of #10 screws? If not, what length screws are to be used? Question #2: At grid line C the ceiling height is approximately 20’10” while at grid line A the ceiling height is approximately 19’2”. Would it be acceptable to use L/120 400S162-33 that span at 23'11" for interior partition walls so that one type of stud can be purchased for the majority of the project. Question #3: Please reference A201.A, S201.A, 1/S401 Drawing S201.A shows stiffeners being required in wall spanning from grid line 9.3/A0.5 to 9.3/B0.5 which are typical for a freewall application as shown in detail 1/S401. Drawing A201.A calls out same wall to be S4.2N> which is a full height wall. Please confirm that wall spanning from grid line 9.3/A0.5 to 9.3/B0.5 only needs to be a full height wall with no freewall stiffeners. Question #4: Per note #2 on 3/S401, please confirm that detail 8/S401 can be used in lieu of 3/S401. Question #5: Per detail 9/S401 would it be acceptable to use 400T150-33 track in lieu of 400T150-43 track? Question #6: Please reference drawing S100 note E8.B. Would it be acceptable to use #8 gauge screws instead of #10 screws for 20 guage studs?

All Replies: SEE PREVIOUS RFI RESPONSE FOR ANSWERS TO QUESTIONS ON THIS SHEET

Turner Construction - Portland

Page 1 of 2

Printed On: 04/25/2016 05 :35 PM

RFI #009 Response from Georg Gold (Turner Construction Company) at 10:26 AM on 04/22/2016 Please reference drawing S301.A, On S301.A on grid line A.5/6 a HDR header is called out to be installed. This header calls out detail 10/S401 which in turn calls out detail 3/S401. Would it be acceptable to use detail 8/S401 in lieu of Header Framing Detail 3/S401 as ceiling gypsum board will be installed in the entry way to mud room 142? VLMK RESPONSE: Please see attached revised framing plan (sheet R-001) for the referenced area. After discussion with HEA, it was Attachments: determined that the headers are needed to prevent the necessity of a vertical drywall joint at either end of the span (due to roof deflection concerns of adjacent/continuous floor-supported and roof-suspended wall surfaces). Attachments: Response from

Camilla Cok (Hennebery Eddy Architects) at 02:33 PM on 04/20/2016

Please see answers to the questions in the attached RFI response. Let me know if you have any questions Attachments:from Camilla Cok (Hennebery Eddy Architects) at 02:33 PM on 04/20/2016 Response NTF_RFI 009 - Structural Framing - VLMK, HEA Response 04-20-16.pdf Please see answers to the questions in the attached RFI response. Let me know if you have any questions Attachments: NTF_RFI 009 - Structural Framing - VLMK, HEA Response 04-20-16.pdf

VLMK - CGA BY

Turner Construction - Portland

04-26-16 DATE

COPIES TO

Page 2 of 2

Printed On: 04/25/2016 05:35 PM

A

R-001

Sheet S301.A 04/26/16 RFI-009 Revised Framing Plan Nike Bruin (Evergreen I) TI VLMK Engineering & Design - By:CGA

5 TYP S401

10 S401 HDR 11 S401

11 S401

HDR

HDR HDR

FOR JOIST SIZE AND ATTACHMENT SEE DETAIL

10 S401

9 S401

6

09 -0 FI R 16 6-2 04