RFI #451

Report 6 Downloads 49 Views
RFI #451

Project: 1402 - Boston Public Library - Johnson Building Phase 2 700 Bolyston Street Boston, Massachusetts 02116

 

ETR Emergency Lighting L50 & B29 TO:

Elizabeth  Bondaryk (William Rawn Associates, Architects, In)

FROM:

Moritz Schmid (Consigli Construction Co., Inc) 72 Sumner Street Milford, Massachusetts 01757

DATE INITIATED:

05/11/ 2016

STATUS:

Open

LOCATION:

B29

DUE DATE:

05/18/2016

COST CODE:

REFERENCE:

COST IMPACT:

SCHEDULE IMPACT:

DRAWING NUMBER: E2-2L, E2-2B

SPEC SECTION:

RECEIVED FROM:

Matt Maher (Wayne J. Griffin Electric Inc.)

COPIES TO: Jose J. Ayala (Consigli Construction Co., Inc), Elizabeth  Bondaryk (William Rawn Associates, Architects, In), Philip  Brault (Consigli Construction Co., Inc), Chris  Carroll (PMA Construction Services), Timothy Cheney (PMA Construction Services), Paul Galligan (Consigli Construction Co., Inc), Matt Gulino (Consigli Construction Co., Inc), Matt Harting (Consigli Construction Co., Inc), Andrew  Jonic (William Rawn Associates, Architects, In), Ned McGrath (PCM), James McQueen (PCM), Jim Meade (BPL), Sindu Meier (William Rawn Associates, Architects, In), Jeff Olinger (William Rawn Associates, Architects, In), Tony Oliva (PMA Construction Services), Moritz Schmid (Consigli Construction Co., Inc), Eamon Shelton (BPL), Mark Suscovich (Consigli Construction Co., Inc), Robert Wear (William Rawn Associates, Architects, In) 

Question from Moritz Schmid (Consigli Construction Co., Inc) at 09:02 AM on 05/11/2016 The lighting drawings call out for existing to remain lighting in L50 and B29. Per the walk through on 5-11 L50 does not have any emergency lighting or exit signs. B29 has (1) emergency fixture outside the door to the mechanical room. Please confirm if there is to be any additional emergency lighting in these locations as they would be needed for the walk through with BFD on 5-16. 

  All Replies: 

The scope of this project did not include replacing lighting in corridors L50 and B29. However, IBC 2009 1006.3 requires that means of egress, including corridors, have emergency electrical power for illumination. See attached code reference. WRA/Cosentini 2016-05-11

BY

Page 1 of 1

DATE

COPIES TO

72 Sumner Street Milford, Massachusetts 01757

Printed On: 05/11/2016 02:43 PM