Redstar Standby - 14 - Redstar Equipment

Report 5 Downloads 213 Views
PH 1800 REDSTAR www.redstarequipment.com.au

Redstar Standby - 14 DIESEL GENERATING SET 400/230 V - 50 Hz SPECIFICATIONS 14 kVA / 11.2 kW Controller

POWERED by PERKINS DEEP SEA 6020 AMF

MODEL Power Standby Prime

RSB-14 Pf. 0.8 14 kVA/11.2 kW 12.5 kVA/10.5 kW

ENGINE - PERKINS Model Engine Power Output at rated rpm Aspiration and Cooling Total Displacement Litre No. of Cylinders and Build Engine Speed rpm Bore and Stroke mmxmm Compression Ratio Governor Fuel Consumption at 50,75 &100 L /hr Fuel Tank Capacity Litre Oil Capacity Litre Coolant Capacity Litre Radiator Cooling Air m³/min Air Intake – Engine m³/min Exhaust Gas Flow m³/min

403D-15G 13.3 kWm/17.8 HP Natural 1.496 3 - Inline 1500 84x90 22.5:1 Mechanical 4.4 , 5.5 & 6.8 44 6 6 36.6 1.08 2.72

ALTERNATOR - STAMFORD Design Stator Rotor Insulation System Standard Temperature Rise Exciter Type Phase Rotation Alternator Cooling AC Waveform Total Harmonic Distortion Telephone Influence Factor (TIF) Telephone Harmonic Factor (THF)

Brushless single bearing, revolving field 2/3 pitch Single bearing, flexible disc Class H 125 - 163°C Continuous Self Excited A (U), B (V), C (W) Direct drive centrifugal blower fan No load < 1.5%. Non distorting balanced linear load < 5%