Submittal Transmittal

Report 18 Downloads 93 Views
HGA, Inc

Submittal Transmittal Submittal ID:

262816-1.0-00001

Transmittal ID:

00121

Date Sent:

9/7/2016

Project:

3536-003-00 Ascension-St Vincent Ambulatory Brownsb

Number:

3536-003-00

To:

Wes Robledo United States (Phone) (Fax)

From:

Margaret Burton HGA, Inc 414-278-3370 (Phone) 414-270-7370 (Fax)

Subject:

Enclosed Switches and Circuit Breakers - Product Data

Via:

Email

Purpose:

Conditionally Approved

Description of Contents Quantity 1

Title Enclosed Switches and Circuit Breakers - Product Data

Number

Date 9/7/2016

Scale

Size

Page 1 of 1

SUBMITTALS FOR:

St. Vincent Ambulatory Center

JOB NO.:

160044

SUBMITTAL NO:

14

SPECIFICATION/SECTION:

262816

TYPE OF MATERIAL:

Enclosed Switches & Circuit Breakers

DATE SUBMITTED:

8/15/16

ARCHITECT & ENGINEER:

Hammel, Green and Abrahamson, Inc. 333 East Erie Street Milwaukee, WI 53202 (414) 278-8200

GENERAL CONTRACTOR:

Turner Construction 55 E Monroe, Suite 1430 Chicago, IL 60603

ELECTRICAL CONTRACTOR:

Electric Plus, Inc. 101 W. Lincoln St. Danville, IN. 46122 (317) 718-0100

This stamp hereby certifies that the attached submittal(s) have been reviewed and checked; therefore these submittals are approved or have been noted otherwise for compliance with the Contract Documents. Project Name: Project Location: Submittal Info:

Prepared By: Date

St Vincent Ambulatory Center Brownsburg, IN Submittal #: Spec. Section Title & No.:

14 Enclosed Switches & Circuit Breakers 262816

Reviewer:

Zach Lone ELECTRIC PLUS, INC.

8/15/16

St. Vincent Brownsburg #160744 01 Submittal # __________________ Spec Section # ___________ 262816 Revision #____________ 00 Reviewed for general acceptance only. This review does not relieve the subcontractor of the responsibility for making the work conform to the requirements of the contract.

Wesley Robledo 08/15/2016 9:27:43 AM

HGA APPROVED

No exceptions noted.

CONDITIONALLY ACCEPTED Exceptions noted, resubmission not required.

See continuation sheet.

NOT APPROVED

See continuation sheet.

RECEIVED For information only

See continuation sheet.

Complete and / or make corrections noted and RESUBMIT

NOT REVIEWED

Not a required submittal.

OTHER ACTION BY

AAS

DATE RECEIVED

8/15/2016

DATE ACTED

9/7/2016

REVIEWED, APPROVED OR ACTED UPON ONLY FOR COMFORMANCE WITH THE INFORMATION GIVEN AND THE DESIGN CONCEPT AS EXPRESSED IN THE CONTRACT DOCUMENTS. NOT REVIEWED FOR SUBMISSION FOR, OR DEVIATION FROM, THE REQUIREMENTS OF THE CONTRACT DOCUMENTS, OR FOR DETERMINING THE ACCURACY AND COMPLETENESS OF OTHER INFORMATION SUCH AS DIMENSIONS (INCLUDING FIELD MEASUREMENTS), QUANTITIES OR INSTALLATION, FABRICATION, OR PERFORMANCE OF EQUIPMENT OR SYSTEMS.

COMMENTS: 1. GENERAL - ALL enclosed circuit breakers are conditionally approved pending outcome of short circuit, arc flash, and coordination studies. 2. ECB-XRAY-A: CONDITIONALLY APPROVED - COORDINATE WITH VENDOR'S SITE SPECIFIC DRAWINGS.

3. ECB-CT: NOT RECIEVED, NOT REVIEWED 4. ECB-MRI: NOT RECIEVED, NOT REVIEWED 5. ECB-EQ: APPROVED 6. ECB-CR: APPROVED 7. ECB-LS: CONDITIONALLY APPROVED; Provide ECB-LS with 150-amp trip 8. NON-FUSED DISCONNECTS: APPROVED

St Vincent Brownsburg Enclosed Switches and Circuit Breakers Approval Drawing Package Factory Order #: 38381502 08/04/2016

Contractor/Installer: Electric Plus Chris Katzfey Sales Representative Isadora Bottino Project Manager North American Operating Division (317) 598-4707 [email protected]

Life Is �n

Scb,fleider c, Electric

TABLE OF CONTENTS ENCLOSED SWITCHES AND CIRCUIT BREAKERS BILL OF MATERIALS AND DRAWINGS HU364RB HU361RB HU361 L600AWK J250S H FRAME DRAWING LITERATURE PowerPact L-Frame Circuit Breakers PowerPact H-Frame Circuit Breakers PowerPact Circuit Breakers - Accessories Circuit Breaker Enclosures - Accessories Micrologic Trip Units for PowerPact Circuit Breakers Brochure Safety Switch Accessories Handout

Q2C Number: 38381502

Quote Number: 1

Project Name: ST. VINCENT BROWNSBURG Item No.

Qty.

Catalog Number / Details

ENCLOSED SWITCHES AND CIRCUIT BREAKERS 027-00

3

Designation: ECB-EQ, CR, LS LJL36400U31X MOLDED CASE CIRCUIT BREAKER 600V 400A LJL36400U31X UL/CSA Rated PowerPact L Frame Termination: Lugs Line/Load Side 3 Pole Device 400 Amp Capacity 600 Vac Rated 80% Rated - Standard rated Interrupting Rating 100kA @ 240Vac/65kA @ 480Vac/25kA @ 600Vac Micrologic Basic Trip Unit - LI Revision - 6/7/2016 - (20160524/20160524) 6/9/2016 3:09:20 PM

028-00

3

Designation: ECB-EQ, CR, LS L600AWK ENCLOSURE POWERPACT L BREAKERS TYPE 12

029-00

3

Designation: ECB-EQ, CR, LS SN400LA NEUTRAL ASSEMBLY INSULATED GROUNDABLE

030-00

3

Designation: ECB-EQ, CR, LS PKOGTA4 HDSS EQUIPMENT GROUND ASSY

031-00

1

Designation: ECB-XRAY-A HDL36125SA MOLDED CASE CIRCUIT BREAKER 600V 125A HDL36125SA UL/CSA Rated PowerPact H Frame Termination: Lugs Line/Load Side 125 Amp Capacity 3 Pole Device 600 Vac Rated 80% Rated - Standard rated Interrupting Rating 25kA @ 240Vac/18kA @ 480Vac/14kA @ 600Vac Shunt Trip 110-130Vac Revision - 6/7/2016 - (20160524/20160524) 6/9/2016 3:12:05 PM

032-00

1

Designation: ECB-XRAY-A J250S ENCLOSURE FOR CIRCUIT BREAKER NEMA 1

033-00

1

Designation: ECB-XRAY-A SN400LA NEUTRAL ASSEMBLY INSULATED GROUNDABLE

Revision Number: 0 Quote Name: AMBULATORY CENTER

Q2C Number: 38381502

Quote Number: 1

Project Name: ST. VINCENT BROWNSBURG Item No.

Qty.

034-00

1

Designation: ECB-XRAY-A PKOGTH150 J250 ENCB GND LUG 15-150 AMP KIT

035-00

3

Designation: RTU HU364RB SWITCH NONFUSIBLE HD 600V 200A 3P NEMA3R

036-00

3

PKOGTA2 EQUIP GRD ASSY 240V + 600V 100-200

037-00

9

Designation: ACC, EF HU361RB SWITCH NOT FUSIBLE HD 600V 30A 3P NEMA3R

038-00

70

Designation: CRU,CUH,EF,H,TF,UH,VA HU361 SWITCH NOT FUSIBLE HD 600V 30A 3P NEMA1

039-00

79

GTK03 KIT EQUIPMENT GROUND CU/AL

Catalog Number / Details

Revision Number: 0 Quote Name: AMBULATORY CENTER

PowerPact™ Molded Case Circuit Breakers

L-Frame Circuit Breakers Class 611 / Refer to Catalogs: 0611CT1001 schneider-electric.us

PowerPact L-Frame Molded Case Circuit Breakers Table 7.64: L-Frame 600 A Standard (80% Rated) UL Current-Limiting [23] Circuit Breakers with Lugs and Factory-Sealed Electronic Trip Units Suitable for Reverse Connection [24][25] Electronic Trip Unit Type Trip Unit Function 600 Vac, 50/60 Hz, 3P Micrologic Standard

LI

3.3 [26]

Micrologic Standard

LSI

3.3S [26]

Micrologic Ammeter Micrologic Energy

LSI

5.3A

LSI

5.3E

Micrologic LSIG Ammeter Micrologic LSIG Energy 600 Vac, 50/60 Hz, 4P

6.3A 6.3E

Micrologic Standard

LI

Micrologic Standard

LSI

3.3S

LSI

5.3A

Micrologic Ammeter Micrologic Energy Micrologic Ammeter Micrologic Energy

3.3

LSI

5.3E

LSIG

6.3A

LSIG

6.3E

Interrupting Rating (80% Rated) J [23]

Sensor Rating

D

G

250 A 400 A 600 A 250 A 400 A 600 A 400 A 600 A 400 A 600 A 400 A 600 A 400 A 600 A

LDL36250U31X LDL36400U31X LDL36600U31X LDL36250U33X LDL36400U33X LDL36600U33X LDL36400U43X LDL36600U43X LDL36400U53X LDL36600U53X LDL36400U44X LDL36600U44X LDL36400U54X LDL36600U54X

LGL36250U31X LGL36400U31X LGL36600U31X LGL36250U33X LGL36400U33X LGL36600U33X LGL36400U43X LGL36600U43X LGL36400U53X LGL36600U53X LGL36400U44X LGL36600U44X LGL36400U54X LGL36600U54X

250 A 400 A 600 A 250 A 400 A 600 A 400 A 600 A 400 A 600 A 400 A 600 A 400 A 600 A

LDL46250U31X LDL46400U31X LDL46600U31X LDL46250U33X LDL46400U33X LDL46600U33X LDL46400U43X LDL46600U43X LDL46400U53X LDL46600U53X LDL46400U44X LDL46600U44X LDL46400U54X LDL46600U54X

LGL46250U31X LGL46400U31X LGL46600U31X LGL46250U33X LGL46400U33X LGL46600U33X LGL46400U43X LGL46600U43X LGL46400U53X LGL46600U53X LGL46400U44X LGL46600U44X LGL46400U54X LGL46600U54X

L [23]

R [23]

LJL36250U31X LJL36400U31X LJL36600U31X LJL36250U33X LJL36400U33X LJL36600U33X LJL36400U43X LJL36600U43X LJL36400U53X LJL36600U53X LJL36400U44X LJL36600U44X LJL36400U54X LJL36600U54X

LLL36250U31X LLL36400U31X LLL36600U31X LLL36250U33X LLL36400U33X LLL36600U33X LLL36400U43X LLL36600U43X LLL36400U53X LLL36600U53X LLL36400U44X LLL36600U44X LLL36400U54X LLL36600U54X

LRL36250U31X LRL36400U31X LRL36600U31X LRL36250U33X LRL36400U33X LRL36600U33X LRL36400U43X LRL36600U43X LRL36400U53X LRL36600U53X LRL36400U44X LRL36600U44X LRL36400U54X LRL36600U54X

LJL46250U31X LJL46400U31X LJL46600U31X LJL46250U33X LJL46400U33X LJL46600U33X LJL46400U43X LJL46600U43X LJL46400U53X LJL46600U53X LJL46400U44X LJL46600U44X LJL46400U54X LJL46600U54X

LLL46250U31X LLL46400U31X LLL46600U31X LLL46250U33X LLL46400U33X LLL46600U33X LLL46400U43X LLL46600U43X LLL46400U53X LLL46600U53X LLL46400U44X LLL46600U44X LLL46400U54X LLL46600U54X

LRL46250U31X LRL46400U31X LRL46600U31X LRL46250U33X LRL46400U33X LRL46600U33X LRL46400U43X LRL46600U43X LRL46400U53X LRL46600U53X LRL46400U44X LRL46600U44X LRL46400U54X LRL46600U54X

Terminal AL400L61K3 [27] AL600LS52K3 [28] AL400L61K3 [27] AL600LS52K3 [28]

AL600LS52K3 [28]

AL400L61K4 [27] AL600LS52K4 [28] AL400L61K4 [27] AL600LS52K4 [28]

AL600LS52K4 [28]

Table 7.65: L-Frame 600 A 100% Rated UL Current-Limiting [23] Circuit Breakers with Lugs and Factory-Sealed Electronic Trip Units Suitable for Reverse Connection [24][25] Electronic Trip Unit Type Function 600 Vac, 50/60 Hz, 3P

Trip Unit

Micrologic Standard

LI

3.3 [26]

Micrologic Standard

LSI

3.3S [26]

Micrologic Ammeter Micrologic Energy Micrologic Ammeter Micrologic Energy 600 Vac, 50/60 Hz, 4P

LSI LSI LSIG LSIG

5.3A 5.3E 6.3A 6.3E

Micrologic Standard

LI

3.3

Micrologic Standard

LSI

3.3S

Micrologic Ammeter Micrologic Energy Micrologic Ammeter Micrologic Energy

LSI LSI LSIG LSIG

5.3A 5.3E 6.3A 6.3E

Interrupting Rating (100% Rated) J [23]

Sensor Rating

D

G

250 A 400 A 250 A 400 A 400 A 400 A 400 A 400 A

LDL36250CU31X LDL36400CU31X LDL36250CU33X LDL36400CU33X LDL36400CU43X LDL36400CU53X LDL36400CU44X LDL36400CU54X

LGL36250CU31X LGL36400CU31X LGL36250CU33X LGL36400CU33X LGL36400CU43X LGL36400CU53X LGL36400CU44X LGL36400CU54X

250 A 400 A 250 A 400 A 400 A 400 A 400 A 400 A

LDL46250CU31X LDL46400CU31X LDL46250CU33X LDL46400CU33X LDL46400CU43X LDL46400CU53X LDL46400CU44X LDL46400CU54X

LGL46250CU31X LGL46400CU31X LGL46250CU33X LGL46400CU33X LGL46400CU43X LGL46400CU53X LGL46400CU44X LGL46400CU54X

Terminal

L [23]

R [23]

LJL36250CU31X LJL36400CU31X LJL36250CU33X LJL36400CU33X LJL36400CU43X LJL36400CU53X LJL36400CU44X LJL36400CU54X

LLL36250CU31X LLL36400CU31X LLL36250CU33X LLL36400CU33X LLL36400CU43X LLL36400CU53X LLL36400CU44X LLL36400CU54X

LRL36250CU31X LRL36400CU31X LRL36250CU33X LRL36400CU33X LRL36400CU43X LRL36400CU53X LRL36400CU44X LRL36400CU54X

AL400L61K3 [27] AL600LS52K3 [28] AL400L61K3 [27] AL600LS52K3 [28]

LJL46250CU31X LJL46400CU31X LJL46250CU33X LJL46400CU33X LJL46400CU43X LJL46400CU53X LJL46400CU44X LJL46400CU54X

LLL46250CU31X LLL46400CU31X LLL46250CU33X LLL46400CU33X LLL46400CU43X LLL46400CU53X LLL46400CU44X LLL46400CU54X

LRL46250CU31X LRL46400CU31X LRL46250CU33X LRL46400CU33X LRL46400CU43X LRL46400CU53X LRL46400CU44X LRL46400CU54X

AL400L61K4 [27] AL600LS52K4 [28] AL400L61K4 [27] AL600LS52K4 [28]

AL600LS52K3 [28]

AL600LS52K4 [28]

Table 7.66: Termination Options

7 MINIATURE AND MOLDED CASE CIRCUIT BREAKERS

L-Frame Circuit Breaker

Termination Letter A F L M P N D S

Termination Option I-Line (See Section 9) No lugs Lugs both ends Lugs ON end, terminal nut kit OFF end Lugs OFF end, terminal nut kit ON end Plug In Drawout Rear Connected

For factory-installed termination, place termination letter in the third block of the circuit breaker catalog number. Termination Letter LGL36600U44X

Table 7.67: Interrupting Ratings Accessories see page 7-59 Optional Lugs see page 7-64 Dimensions see page 7-80 Enclosures see page 7-81

[23] [24] [25] [26] [27] [28] 7-36

Voltage 240 Vac 480 Vac 600 Vac

D 25 kA 18 kA 14 kA

G 65 kA 35 kA 18 kA

Interrupting Rating J 100 kA 65 kA 25 kA

L 125 kA 100 kA 50 kA

R 200 kA 200 kA 100 kA

Circuit breakers with J, L, and R interrupting ratings are UL certified as current limiting. See Supplemental Digest Section 3 for circuit breakers with field interchangeable trip units. For applications requiring communications see page 7-73. 3P circuit breakers with this trip unit can be used for 2P applications. AL400L61K3 terminal wire ranges are (1) 2 AWG–600 kcmil Cu or 1) 2 AWG–500 kcmil Al. AL600LS52K3 terminal wire range is (2) 2/0 AWG–500 kcmil Al/Cu. © 2015 Schneider Electric All Rights Reserved

THIS PAGE WAS INTENTIONALLY LEFT BLANK

H- and J-Frame Circuit Breakers

PowerPact™ Molded Case Circuit Breakers

Class 611 / Refer to Catalog 0611CT1001 schneider-electric.us

PowerPact H- and J-Frame Circuit Breakers

HD and HG 2P Thermal-Magnetic Trip Unit (2P HJ, HL in 3P module)

H-Frame Thermal-Magnetic Trip Unit

Table 7.53: H-Frame 150 A Thermal-Magnetic UL Current-Limiting [5] Circuit Breakers (600 Vac, 250 Vdc) [6] With Factory Sealed Trip Unit Suitable for Reverse Connection [7]

Standard (80% Rated) H-Frame, 150A 2P, 600 Vac 50/60 Hz, 250 Vdc [8] 15 A 350 A  750 A HDL26015 20 A 350 A  750 A HDL26020 25 A 350 A  750 A HDL26025 30 A 350 A  750 A HDL26030 35 A 400 A  850 A HDL26035 40 A 400 A  850 A HDL26040 45 A 400 A  850 A HDL26045 50 A 400 A  850 A HDL26050 60 A 800 A 1450 A HDL26060 70 A 800 A 1450 A HDL26070 80 A 800 A 1450 A HDL26080 90 A 800 A 1450 A HDL26090 100 A 800 A 1700 A HDL26100 110 A 900 A 1700 A HDL26110 125 A 900 A 1700 A HDL26125 150 A 900 A 1700 A HDL26150 H-Frame 150A 3P, 600 Vac 50/60 Hz, 250 Vdc 15 A 350 A  750 A HDL36015 20 A 350 A  750 A HDL36020 25 A 350 A  750 A HDL36025 30 A 350 A  750 A HDL36030 35 A 400 A  850 A HDL36035 40 A 400 A  850 A HDL36040 45 A 400 A  850 A HDL36045 50 A 400 A  850 A HDL36050 60 A 800 A 1450 A HDL36060 70 A 800 A 1450 A HDL36070 80 A 800 A 1450 A HDL36080 90 A 800 A 1450 A HDL36090 100 A 800 A 1700 A HDL36100 110 A 900 A 1700 A HDL36110 125 A 900 A 1700 A HDL36125 150 A 900 A 1700 A HDL36150

[5] [6] [7] [8]

Hold

Trip

Interrupting Rating D

J [6]

G

L [6]

100% Rated

Standard (80% Rated)

100% Rated

Standard (80% Rated)

100% Rated

Standard (80% Rated)

100% Rated

HDL26015C HDL26020C HDL26025C HDL26030C HDL26035C HDL26040C HDL26045C HDL26050C HDL26060C HDL26070C HDL26080C HDL26090C HDL26100C HDL26110C HDL26125C HDL26150C

HGL26015 HGL26020 HGL26025 HGL26030 HGL26035 HGL26040 HGL26045 HGL26050 HGL26060 HGL26070 HGL26080 HGL26090 HGL26100 HGL26110 HGL26125 HGL26150

HGL26015C HGL26020C HGL26025C HGL26030C HGL26035C HGL26040C HGL26045C HGL26050C HGL26060C HGL26070C HGL26080C HGL26090C HGL26100C HGL26110C HGL26125C HGL26150C

HJL26015 HJL26020 HJL26025 HJL26030 HJL26035 HJL26040 HJL26045 HJL26050 HJL26060 HJL26070 HJL26080 HJL26090 HJL26100 HJL26110 HJL26125 HJL26150

HJL26015C HJL26020C HJL26025C HJL26030C HJL26035C HJL26040C HJL26045C HJL26050C HJL26060C HJL26070C HJL26080C HJL26090C HJL26100C HJL26110C HJL26125C HJL26150C

HLL26015 HLL26020 HLL26025 HLL26030 HLL26035 HLL26040 HLL26045 HLL26050 HLL26060 HLL26070 HLL26080 HLL26090 HLL26100 HLL26110 HLL26125 HLL26150

HLL26015C HLL26020C HLL26025C HLL26030C HLL26035C HLL26040C HLL26045C HLL26050C HLL26060C HLL26070C HLL26080C HLL26090C HLL26100C HLL26110C HLL26125C HLL26150C

HDL36015C HDL36020C HDL36025C HDL36030C HDL36035C HDL36040C HDL36045C HDL36050C HDL36060C HDL36070C HDL36080C HDL36090C HDL36100C HDL36110C HDL36125C HDL36150C

HGL36015 HGL36020 HGL36025 HGL36030 HGL36035 HGL36040 HGL36045 HGL36050 HGL36060 HGL36070 HGL36080 HGL36090 HGL36100 HGL36110 HGL36125 HGL36150

HGL36015C HGL36020C HGL36025C HGL36030C HGL36035C HGL36040C HGL36045C HGL36050C HGL36060C HGL36070C HGL36080C HGL36090C HGL36100C HGL36110C HGL36125C HGL36150C

HJL36015 HJL36020 HJL36025 HJL36030 HJL36035 HJL36040 HJL36045 HJL36050 HJL36060 HJL36070 HJL36080 HJL36090 HJL36100 HJL36110 HJL36125 HJL36150

HJL36015C HJL36020C HJL36025C HJL36030C HJL36035C HJL36040C HJL36045C HJL36050C HJL36060C HJL36070C HJL36080C HJL36090C HJL36100C HJL36110C HJL36125C HJL36150C

HLL36015 HLL36020 HLL36025 HLL36030 HLL36035 HLL36040 HLL36045 HLL36050 HLL36060 HLL36070 HLL36080 HLL36090 HLL36100 HLL36110 HLL36125 HLL36150

HLL36015C HLL36020C HLL36025C HLL36030C HLL36035C HLL36040C HLL36045C HLL36050C HLL36060C HLL36070C HLL36080C HLL36090C HLL36100C HLL36110C HLL36125C HLL36150C

MINIATURE AND MOLDED CASE CIRCUIT BREAKERS

Fixed AC Magnetic Trip

Circuit breakers with J and L interrupting ratings are UL certified as current limiting. Standard lug kit: AL150HD. Terminal wire range: 14–3/0 AWG Al or Cu. See Supplemental Digest Section 3 for circuit breakers with field interchangeable trip units. HD and HG circuit breakers are true two-pole construction.

© 2015 Schneider Electric All Rights Reserved

7-31

7

Current Rating @ 40o C

THIS PAGE WAS INTENTIONALLY LEFT BLANK

Electrical Accessories

PowerPact™ Circuit Breaker Accessories

Class 612 / Refer to Catalog 0612CT0101 schneider-electric.us

PowerPact Accessories Table 7.125: Electrical Accessories

Accessory

Description

Auxiliary and Alarm Switches (OF, SD, SDE) Standard Min Load = 10mA with 24V

B-Frame

Provides circuit breaker contact status. Note: The location of the accessory in the circuit breaker determines its function. Low Level Min Load = 1mA with 24V

H-, J-, L-, M-, P, and R-Frame Shunt Trip (MX)

B-Frame

Trips the circuit breaker from a remote location by means of a trip coil energized from a separate supply voltage circuit.

Rated Voltage

1 auxiliary switch (OF) 1a1b 2 auxiliary switch (OF) 2a2b 3 auxiliary switch (OF) 3a3b Alarm Switch (SD) 1a1b Overcurrent trip switch (SDE) 1a1b OF Switch Consisting of: SDE Adapter Alarm switch and Overcurrent trip switch OF Switch Consisting of: SDE Adapter Auxiliary Switch/Alarm Switch/ Adapter (OF/SD/SDE) Kit One auxiliary switch (OF) 1a1b Two auxiliary switches (OF) 2a2b 3 auxiliary switches (OF) 3a3b Alarm Switch (SD) 1a1b Overcurrent trip switch (SDE) 1a1b OF Switch Consisting of: SDE Adapter Alarm switch and Overcurrent trip switch OF Switch Consisting of: SDE Adapter [4] 24 48 110–130 AC 220–240 208–277 380–480 525–600 12 24 30 48 60 125 DC

Factory Installed Cat. Suffix AA AB AC BC

B-, H-, J-, and L-Frame H- and JFrame FieldFieldFieldInstallable Installable Installable Pre-Wired Cat. No. Cat. No. Cat. No. LV426950 LV426951 S29450 — — 2x S29450 — — — LV426950 LV426952 S29450

M-, P-, and R-Frame L-Frame

B-Frame

Factory Installed Cat. Suffix

FieldInstallable Cat. No.

S29450 S29450 S29450 S29450

AA AB AC BC

2x S29450 [1] 3x S29450 [1] S29450 [1]

FieldInstallable Cat. No. 2x 3x

S29450 [1]

BD







S29450

BD

S29450 [1]

— —

— —

— —

S29450 S29451

— —

— —

— —

S29450

BE

— —

— —

— — S33801 [2]

BE





— —

— —

— —



2x

2x S29450 S29451

2x S29450













AE





S29452

S29452

AE

S29452

AF





2x S29452

2x

S29452

AF

2x S29452

AG BH

— —

— —

— S29452

3x

S29452 S29452

AG BH

3x S29452 S29452

BJ







S29452

BJ [3]

S29452

— —

— —

— —

S29452 S29451

— —

— —

— —

BK





S29452

BK [3]

— — SK SL SA — SD SH SJ SN SO SU SP SV SR

— — LV426841 LV426842 LV426843 — LV426844 LV426846 — — LV426841 — LV426842 — LV426843

— — LV426861 LV426862 LV426863 — LV426864 LV426866 — — LV426861 — LV426862 — LV426863

2x S29452 S29451 S29384 S29385 S29386 — S29387 S29388 S29389 S29382 S29390 S29391 S29392 S29383 S29393

— — S29384 S29385 S29386 — S29387 S29388 S29389 S29382 S29390 S29391 S29392 S29383 S29393

— — SK SL SA SC SD SH — SN SK SK SL SL SA

— — S33659 S33660 S33661 S33662 S33663 S33664 — S33658 S33659 S33659 S33660 S33660 S33661

250

SS

LV426844

LV426864

S29394

S29394

SC

S33662

24 48 110–130 220–240 208–277 380–415 380–480 525–600 12 24 30 48 60 125 250 48 100–130 220–250

UK UL UA UC UD UF UH UJ UN UO UU UP UV UR US — — —

LV426801 LV426802 LV426803 LV426804 LV426805 LV426806 LV426807 — — LV426801 — LV426802 — LV426803 LV426815 S33680 [5] S33681 [5] S33682 [5]

LV426821 LV426822 LV426823 LV426824 LV426825 LV426826 LV426827 — — LV426821 — LV426822 — LV426823 LV426835 — — —

S29404 S29405 S29406 — S29407 — S29408 S29409 S29402 S29410 S29411 S29412 S29403 S29413 S29414 S33680 [5] S33681 [5] S33682 [5]

S29404 S29405 S29406 — S29407 — S29408 S29409 S29402 S29410 S29411 S29412 S29403 S29413 S29414 S33680 [5] S33681 [5] S33682 [5]

UK UL UA UC — — UH — — UK UK UL UL UA UC — — —

S33668 S33669 S33670 S33671 — — S33673 — — S33668 S33668 S33669 S33669 S33670 S33671 S33680 [5] S33681 [5] S33682 [5]





S33683 [5]

S29426 [5] — — S29427 [5]

— — — —

— S33684 [5] S33685 [5] —



2x

2x S29452

Time Delay Unit

[1] [2] [3] [4] [5]

Undervoltage trip with externally mounted adjustable time delay unit for UVR of 0.5, 0.9, 1.5, 3.0 seconds before circuit breaker trips Undervoltage trip with externally mounted nonadjustable time delay unit of 0.25 sec before circuit breaker trips.

AC

DC

AC/DC

AC/DC

380–480







48 100–130 200–250 220–240

— — — —

S29426 [5] — — S29427 [5]

— — — —

— S29426 [5] — — S29427 [5]

For electrically-operated P-frame circuit breakers S29450 is not field installable. P-frame drawout circuit breaker only. Not available on electrically operated P-frame. SDE Adapter used for H- and J-frame only. Field-installable kit includes time delay module only. Order undervoltage trip separately.

© 2015 Schneider Electric All Rights Reserved

7-59

7

Undervoltage Trip (MN) H-, J-, and L-Frame

Instantaneously opens the circuit breaker when the under-voltage trip supply voltage drops to a value between 35% and 70% of its rated voltage. Closing is allowed when the supply voltage of the undervoltage trip reaches 85% of rated voltage.

MINIATURE AND MOLDED CASE CIRCUIT BREAKERS

H-, J-, and L-Frame

THIS PAGE WAS INTENTIONALLY LEFT BLANK

Enclosure Accessories and Dimensions

Circuit Breaker Enclosures

Class 610 schneider-electric.us

Enclosure Accessories Table 7.187: Neutral Kit Terminal Data Neutral Kit Catalog Number 100SNA SN100FA SN225KA 225SNA 400SN SN400LA SN1000MA SNC400LX SNC800LX AL800SN SN1200 S33576MK

Terminal Lug Data -Total Available (Line plus Load) AWG/kcmil AL/CU (2) 14–1/0 Cu or (2) 12–1/0 Al plus (1) 14–4 Cu (4) 14–1/0 Cu or (4) 12–1/0 Al (2) 4–300 Al/Cu plus (2) 14–1/0 Al/Cu (4) 6–350 Al/Cu (2) 1–600 or (4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu (2) 1–600 or (4) 1–250 Al/Cu, plus (2) 4–300 Al/Cu (6) 3/0–500 Al/Cu, plus (1) 1–4/0 Al/Cu — — (6) 3/0–500 Al/Cu, plus (2) 6–250 Al/Cu (8) 3/0–750 Al/Cu, plus (2) 6–350 Al/Cu (8) 3/0–500 Al/Cu, plus (2) 4–300 Al/Cu

All Copper Neutral Terminal Lug Data -Total Available (Line plus Load) AWG/kcmil — — — — — — — (2) 2–-600 Cu, plus (2) 6–250 Cu (4) 2–600 Cu, plus (1) 2–4/0 Cu — — —

Table 7.188: Service Ground Kit Terminal Data Service Ground Kit Catalog Number PKOGTA2 PKOGTH150 PKOGTJ250 PKOGTA4

Terminal Data AWG/kcmil 10–2/0 Cu or 6–2/0 Al 14–2 Al/Cu 6–300 Al/Cu 6–250 Al/Cu

Lugs Per Kit 2 1 2 4

© 2015 Schneider Electric All Rights Reserved

7-85

7

MINIATURE AND MOLDED CASE CIRCUIT BREAKERS

See Supplemental Digest Section 3 for special options for enclosures: • Stainless steel fronts • Pilot lights, push buttons • Lock-on SPL0 • Key interlock systems • Legend plates

THIS PAGE WAS INTENTIONALLY LEFT BLANK

Micrologic trip units The full range of PowerPact circuit breakers now feature Micrologic electronic trip units (energy model). Micrologic trip units are the intelligence behind a coordinated electrical distribution system that delivers improved operating efficiency and extended equipment life. All Micrologic trip units provide impeccable, electronic circuit protection with adjustable protection settings for maximum system coordination and flexibility. Sophisticated functionality, such as energy and power quality metering capabilities, is integrated in the more advanced trip units. Combined with quality PowerPact accessories, Micrologic trip units also enable circuit breakers to be networked and remotely controlled leading to substantial savings in electrical system operating costs. These interchangeable, microprocessor controlled devices provide the new generation of protection, measurement and control functions, delivering not only greater electrical system safety but also improved system integration and coordination.

Standard Micrologic trip unit for PowerPact H, J, and L

Micrologic P trip unit for PowerPact P and R

Micrologic E trip unit for PowerPact P and R Micrologic H trip unit for PowerPact P and R Ammeter or Energy trip unit for Powerpact H, J and L

8

Simple: an easy installation and use Choose the model that meets your needs The Micrologic trip unit family includes five models with varying levels of functionality. The simplest units provide basic overcurrent protection including long-time, instantaneous, and optional short-time adjustments for overloads and short circuits. Advanced units offer sophisticated functions such as ground fault protection and zone selective interlocking. They also incorporate a variety of communications options and energy metering capabilities – right inside the circuit breaker. With advanced trip units, use a network to communicate breaker information, gather power information and energy usage patterns, monitor events, and remotely control breakers for increased efficiency and savings. The breakers become part of an integrated, coordinated electrical system. For maximum flexibility in product selection, Micrologic trip units consist of five models with progressively increasing levels of functionality.

Choose the right model for each application PowerPact H-, J- and L-Frame

Standard (S)

Ammeter (A)

Energy (E)

Standard (S)

Ammeter (A)

Energy (E)

15 – 600 A

PowerPact P- and R-Frame

Power (P)

Harmonic (H)

up to 3000 A

Adj. protections True RMS Thermal imaging

Current meter LED trip ind. ZSI

Power and energy meter

Frequency Power factor

Total harmonic distortion

Motor protection trip units Also available are Micrologic trip units dedicated to managing motor applications at 600 A or below. Three levels of functionality are available with the motor trip unit offer. • 1.3M: Provides cable protection for short-circuits, and must be combined with an external thermal protection relay. This trip unit features an adjustable short-circuit protection threshold and fixed instantaneous protection. • 2 M: Provides thermal relay type protection in addition to short-circuit protection. Adjustable settings are included for the thermal protection threshold, the tripping class, and the short-circuit protection. Additional protections include phase unbalance and phase loss protection. • 6 E-M: Provides the same protection functions as the Micrologic 2-M units with the addition of ground fault, locked rotor protection, under-load protection and long start protection. They also incorporate energy metering and maintenance indicators similar to the Micrologic Energy trip unit. 9

Simple: an easy installation and use (continued)

Mounting dimensions Common mounting dimensions across the entire range means that the mounting pattern never has to change even when panel designs change.

PowerPact H- and J-Frame with Micrologic circuit breakers – 15 A to 250 A Well-suited to a wide range of applications, the Powerpact H- and J-Frame molded case circuit breakers feature a full complement of field installable accessories, field installable trip units, and improved interrupting ratings. These molded case circuit breakers deliver unmatched design flexibility and share identical mounting holes, handle locations, trim dimensions, and accessories, allowing customers to standardize equipment designs for 15 A to 250 A applications. PowerPact H- and J-Frame circuit breakers come in many interruption ratings and are designed to limit let-through currents to provide better protection for downstream components. Interrupting ratings (AIR) include D-18 kA, G-35 kA, J-65 kA and L-100 kA at 480 Vac. Available as standard or 100% rated circuit breakers, the H-Frame ranges from 15 A to 150 A and the J-Frame from 70 A to 250 A. Available trip units:

H-Frame and a J-Frame PowerPact circut breaker.

• Thermal magnetic: Circuit protection provided by individual thermal (overload) and magnetic (short circuit) sensing elements in each pole.

Choice of terminal options

• Standard electronic: Adjustable overcurrent protection including long-time, instantaneous, and optional short-time.

Terminal options include unique snap-in lugs that make converting between bus bar and lug options easy. If the application calls for lugs on the line side, load side or both, conversions are simple, making the PowerPact H- and J-Frame circuit breakers ideal for applications that require configuring products at the point of use. The terminal nut or mechanical lug is set on a plastic retainer that slides and snaps into place. Making it possible to easily convert to a distrubution lug that provides multiple cable outputs for downstream components.

Bus bar option

10

Lug option

• Ammeter: Adjustable long-time, short-time, instantaneous and optional ground fault protection is coupled with integrated current metering and maintenance indicators. • Energy: Power and energy metering is integrated with exceptional long-time, shorttime, instantaneous, and optional ground fault protections. Beyond energy metering, this trip unit delivers many advanced functions including power quality (harmonics) measurement.

PowerPact L-Frame with Micrologic circuit breaker – 70 A to 600 A

PowerPact P- and R-Frame with Micrologic circuit breakers – 100 A to 3000 A

Designed to accept common accessories and the full range of electronic trip options available for PowerPact H- and J-Frame, the newest addition to the PowerPact family of molded case circuit breakers delivers the same impeccable protection and flexibility. PowerPact L-Frame is also available as standard or 100% rated, and has a choice of many interruption ratings to support different application needs. Interrupting ratings (AIR) include D-18 kA, G-35 kA, J-65 kA and L-100 kA at 480 Vac.

The compact P- and R-Frame circuit breakers permit smaller footprint and higher density installations. These circuit breakers are available in standard and 100% rated construction up to 3000 A to meet a broad range of commercial and industrial application needs. Common accessories make stocking and installation easy.

Available trip units:

Built-in Modbus™ protocol provides an open communications platform and can be combined with a selection of four interchangeable Micrologic trip units.

• Standard electronic: Adjustable overcurrent protection including long-time, instantaneous, and optional short-time.

• Standard: Adjustable overcurrent protection including long-time, instantaneous, and optional short-time.

• Ammeter: Adjustable long-time, short-time, instantaneous, and optional ground fault protection is coupled with integrated current metering and maintenance indicators.

• Ammeter: Adjustable long-time, short-time, instantaneous, and optional ground fault protection is coupled with integrated current metering and an optional Modbus communication interface.

• Energy: Power and energy metering is integrated with exceptional long-time, shorttime, instantaneous, and optional ground fault protections. Beyond energy metering, this trip unit delivers many advanced functions including power quality (harmonics) measurement.

• Power: Combines power monitoring and metering functions, with long-time, short-time, instantaneous/optional ground fault adjustments, and advanced relay functions, and has a standard Modbus communication interface. • Harmonics: All of the functionality of the Power trip unit, plus enhanced monitoring and metering capabilities, basic power quality (harmonics) measurement, and waveform capture.

PowerPact P-Frame with Micrologic PowerPact L-Frame with Micrologic

PowerPact R-Frame with Micrologic

THIS DOCUMENT HAS BEEN REDACTED FROM A LARGER DOCUMENT (DOC# 0600BR1101 PUBLISHED SEPTEMBER 2011)

11

When installed, this kit rejects all but Class R fuses. Kits are available for field installation. For factory installation, add “CLR’’ suffix to catalog number.

Accessories

Switch Rating (A)

Switch Rating (A)

Series Number (See pages 3-14, 3-15)

30

F1,F5-F6 F1-F3, F5-F7 (600V) F4, F5-F6 (240V)

60

Terminal Data AWG/kcmil

Opitonal Copper Only Neutral Kit Cat. No.

SN03

(3) 2 Max. AI/Cu

SN03C

(3) 6 Max. Cu

SN0610

(2) 1/0Max AI/Cu (2) 6 Max. AI/Cu

SN0610C

(2) 1/0 Max. Cu (2) 6 Max. Cu

SN03

(3) 2 Max. AI/Cu

SN03C

(3) 6 Max. Cu

SN0610C

(2) 1/0 Max. Cu (2) 6 Max. Cu (2) 250 Max.Cu (1) 1/0 Max. Cu

Standard Neutral Kit Cat. No.

100

F2-F6

SN0610

(2) 1/0 Max. AI/Cu (2) 6 Max. AI/Cu

200

F5-F6

SN20A

(2) 250 Max. AI/Cu (1) 1/0 Max. AI/Cu

SN20C

400-600

E1-E4

H600SN

(4) 750 Max AI/Cu (1) 300 Max. AI/Cu

H600SNC

800

E2-E4

H800SNE4

1200

E2-E4

H1200SNE4

(6) 750 Max. AI/Cu (2) 350 Max. AI/Cu (8)750 Max. AI/Cu (2) 350 Max. AI/Cu

Terminal Data AWG/kcmil

_

(2) 600 Max. Cu (2) 350 Max. Cu (1) 250 Max. Cu _

_

_

Note: Neutrals cannot be installed in 4P, 6P, or 200 A NEMA 4X fiberglass reinforced polyester safety switches.

The following Series F5–F6 devices use SN0610(C): H-361-2, H-361-2RB, H-361-2A and H-361-2AWK. For 200% neutral, order (2) neutral kits and (1) SN20NI neutral jumper kit. (2) 350 Max. Al/Cu.

Equipment grounding kits are field-installed and UL Listed in 30–1200 A heavy duty switches. For factory installation of equipment grounding kit, add suffix GL to standard Cat. No. (Example: H361GL). NOTE: Kits are factory-installed standard in 30–200 A series F NEMA 4-4X-5 (stainless) and 12, and in all NEMA 30–200 Series F 4–6P switches. Switch Rating (A)

Series Number (See pages 3-14, 3-15)

Standard Cat. No.

Terminal Data AWG/kcmil

Optional Copper Only Cat. No.

Terminal Data AWG/kcmil

30

F1, F5-F7

GTK03

(2)12 Cu or (2) 10AI Or 4 Max.AI/Cu

GTK03C

1)6 Max.Cu

60

F1-F3 F5-F7(600V)

GTK0610

(2)2/0Max. AI/Cu

GTK0610C

(2)4 Max.Cu

60

F4, F5-F6(240V)

GTK03

(2) 12 Cu or (2)10 AI Or (1) 4 Max. AI/Cu

GTK03C

(1)6 Max.Cu

100

F2-F7

GTK0610

(2) 2/0 Max. AI/Cu

GTK0610C

(2)4 Max.Cu

200

F5-F7

PKOGTA2

(2) 2/0 Max. AI/Cu

PKOGTC2

(4)1/0 Max.Cu

E2-E4

PKOGTA2 (2 Required)

(2) 2/0 Max. AI/Cu

PKOGTC3

-

-

-

-

400-600 800

E2-E4

PKOGTA7

(4)350 Max. AI/Cu

1200

E2-E4

PKOGTA8

(8)350 Max. AI/Cu

Description: 16 oz. Aerosol Paint Can, Square D Gray Cat. No.: Paint PK49SP Note: Shipped in quantities of 6. Optional cover viewing window is positioned over the blades to allow visual verification of “ON-OFF’’ status. Available on 30 through 1200 A heavy duty switches, all NEMA Types. (Not available on NEMA 4X fiberglass reinforced polyester, Krydon® enclosures, or NEMA 7 and 9 devices. PKOGTA2

Factory-installed only: add “VW’’ suffix to the Cat. No.

Class R Fuse Kit Cat. No.

30

F5–F7

RFK03L

60

F1, F2, F3

RFK06

60

F4–F7

RFK03H

100

F2–F7

RFK10

200 400–600

F5–F6 E

HRK1020 HRK4060

H221-2AWK uses RFK06 Class R fuse kit.

Switch Rating (A)

Series Number (See pages 3-14, 3-15)

Class R Fuse Kit

30 30 60 100 200 400-600

F1,F5-F7 F3 F1-F7 F2-F7 F5-F6 E2-E4

RFK03H RFK06 RFK06H RFK10 HRK1020 HRK4060

See page 3-7 for Class R Fuse Kits in NEMA 4X Fiberglass Reinforced Polyester and Krydon switches. The following Series F5–F7 devices use RFK06: H3612, H3612A, H3612AWK, H3612RB, H461, H461DS, H461AWK, H361AWA and H361AWC.

Electrical interlocks for heavy duty 30–1200 A safety switches are available factory-installed or in kit form for field installation. Each kit contains instructions for proper field mounting. A pivot arm operates from switch mechanism, breaking the control circuit before the main switch blades break. Switches with electrical interlocks installed are UL Listed.

For factory-installed electrical interlocks add EI (for one contact) or EI2 (for two contacts) suffix to catalog number. See Supplemental Digest page 2-4 for electrical interlock contact ratings.

Switch Rating (A) 30

60

100-200

The following Series F5–F6 devices use GTK0610(C): H-361-2 and H-361-2RB. 4 and 6 pole 30A F Series. Two required if grounding conductors are run in parallel. PE1A Discount Schedule

Series Number (See pages 3-14, 3-15)

400-1200

Series Number (See pages 3-14, 3-15)

Electrical Interlock Kit Cat. No.

F1,F5-F7

EIK031 EIK032

F3

EIK1 EIK2

F1-F3 F5-F7(600V)

EIK1 EIK2

F4 F5-F6(240V)

EIK031 EIK032

F2-F7

EIK1 EIK2

E1-E4

EIK40601 EIK40602

See page 3-7 for electrical interlocks on NEMA 4X fiberglass reinforced polyester and Krydon Electrical interlock kit catalog numbers with 1 suffix indicates one normally open and one normally closed contact; 2 indicates two normally open and two normally closed contacts. Kits are UL Listed. HU461AWK uses EK3061 or EK3062. The following Series F5–F7 devices use EIK-1, 2: H3612, H3612A, H3612AWK, H3612RB, H461, H461DS, H461AWK, HU461, HU461DS, HU661DS, HU661AWK, H361AWA, H361AWC, HU361AWA and HU361AWC. H362WA, HU362WA, H362WC, H362AWA, HU362AWA, H362AWC, HU362AWC, and H2212AWK use EIK1 or EIK2 electric interlock. Single-pole single-throw interlock kits are rated 1/2 hp @ 110 and 220 Vac.

THIS PAGE WAS INTENTIONALLY LEFT BLANK