Submittal

Report 2 Downloads 319 Views
C 510

Submittal Programmable Thermostat 510

02/12 Zoning

Job __________________________

Replaces: 01/11

Contact _______________________

Designer ______________________

The Programmable Thermostat 510 is a micro-processor based control designed to operate mechanical equipment to deliver heat to a single zone within a hydronic heating system. It can be used with any terminal unit type, including radiant floor, baseboard, and fan coils. This product maintains very accurate and even air temperature with Pulse Width Modulation and Auto Cycling. It is capable of controlling a zone valve or zone pump directly or through a tekmarNet ® 4 Wiring Center or Zone Manager to maintain air temperature and 2 auxiliary temperatures. These temperatures could be floor or remote air.

Front View

Side View

Mounting Base 5/8” (17 mm)

7/8” (23 mm) Wire Access

2–7/8” (73 mm)

1/4” (7 mm)

2–7/8” (73 mm)

13/16” (21 mm)

1–3/8” (36 mm)

Specifications --------------------------------------------------------------------------------------- Energy Saving Features -----------• Programmable Setback Schedule

Programmable Thermostat 510 One Stage Heat Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Relays Sensors –Included –Optional Warranty

D510, U510. C510 Microprocessor control. This is not a safety (limit) control 0.5 lb. (230 g) 2-7/8” H x 2-7/8” W x 13/16” D (73 x 73 x 21 mm) White PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Noncondensing 24 V (ac) ±10%, 60 Hz, 3 VA 24 V (ac) 2 A max, Class 2 NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 None tekmar type #: 070, 072, 073, 076, 077, 079, 083, 084 Limited 3 Year (See D510 for full warranty)

Additional Features -----------------• Auto Heating Cycle • Pulse Width Modulation • CSA C US Approved for use in USA and Canada • Freeze Protection • 2 auxiliary sensor inputs • Slab max. and min. settings with installed slab sensor

SPECIAL REQUIREMENTS N/A www.tekmarcontrols.com

1 of 2

© 2012

C 510 - 02/12

Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram

510

Optional Zone Manager or Wiring Center

316

S1

Sample Electrical diagram Legend

2 3 4 C Com S1

938-01

510

US C 24 V ± 10% 60 Hz 3 VA 24 V (ac) 2 A

Switch Settings: Installer/User

Power: Relay: Class 2

No Power

1 R

One Stage Heat

Programmable Thermostat 510

6 7 Heat

Made in Canada Meets Class B: Canadian ICES FCC Part 15

S1 = Slab Sensor

5 S2

or S1 tN4

C

R

W

or Indoor Sensor

Outdoor Sensor

Wiring Center or Zone Manager

tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2012 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

2 of 2

All specifications are subject to change without notice. Printed in Canada. C 510 - 02/12.