Submittal
C 315
tekmarNet® 4 Wiring Center 315
01/11 Zoning
Job ___________________________
Replaces: New
Contact_ _______________________
Designer_ ______________________
The tekmarNet 4 Wiring Center 315 is designed to provide a zoning solution for heating systems. It can be used in applications ranging from baseboard zones, to remote manifolds for radiant heating. This control energizes up to 6 zone valves. It is capable of providing power for up to 6 tekmarNet ®4, or stand alone thermostats, and energizing their respective 24 V (ac) zones, as well as providing an end switch closure to enable an external device such as a boiler. ®
Front View
Side View
Back View
1/2” Knock-out (x 4)
Zone 3
W tN4
C R Zone 4
W H8001
Input Power: 24 V (ac) ±10% 60 Hz 98 VA Max, Class 2 Control Load: 2 VA End Switch: 24 V (ac) 2 A Zone Output: 2 A per zone 4 A (max) total
Zone 4 Zone 5 Zone 6
Made in Canada tektra 1032-01
tN4 Wiring Center 315 Six Zone Valves Zone 1 C Vlv
Zone 2 C Vlv
Zone 3 C Vlv
A
Zone 4 C Vlv
Zone 5 C Vlv
Zone 6 C Vlv
Zone 6 R C tN4 W
End Switch
W
Zone 2
Zone 5 R C tN4
C R Zone 3
Power
Zone 1 Expansion End Switch Input Power R C tN4 C tN4 X X R C
7/8” (22 mm)
W tN4
W
5–1/2” (140 mm)
C R Zone 2
Zone 1
Use at least 167°F (75°C) conductors
tN4
CL 1–1/8” (30 mm) 5–1/2” (140 mm)
2–1/4” (57 mm)
1/2” x 5/8” (12 mm x 16 mm) Knock-out (x 4)
Ø 1/8” (3 mm)
7/8” x 1/2” (23 mm x 12 mm) Knock-out (x 4)
Specifications------------------------------------------------------ Features--------------------------tN4 Wiring Center 315 Six Zone Valves Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Zone valve load End switch relay Warranty
D315, Q315 Microprocessor control. This is not a safety (limit) control 1.4 lb. (630 g) 5.5” H x 5.5” W x 2.25” D (140 x 140 x 57 mm) Blue PC+ABS plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Noncondensing 24 V (ac) ±10%, 60 Hz, 98 VA, Class 2 24 V (ac) 2 A, maximum combined current (zones 1 to 4): 4 A 24 V (ac) 2 A Limited 3 Year (See D315 for full warranty)
• • • • • •
Six 24 V (ac) powered zone outputs For use with tekmarNet ® 4 thermostats tN4 expansion terminals Isolated end switch External diagnostic LEDs CSA C US Certified for use in USA and Canada
Special requirements
Designed for use with tekmarNet ®4 Thermostats. www.tekmarcontrols.com
of 2
© 2011
C 315 - 01/11
Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram
315
Z1
Z2
tNt
tNt
Z3
tNt
tNt
Z4
tNt
Z5
tNt
tekmarNet® 4 Thermostats
Z6
tekmarNet® 4 Thermostats
Sample Electrical diagram Legend V1 = Balancing valve Z1 = Zone 1 Z2 = Zone 2 Z3 = Zone 3 Z4 = Zone 4 Z5 = Zone 5 Z6 = Zone 6 End Switch = Provides boiler demand on reset control (e.g. tekmar Boiler Control 260)
W H8001
Input Power: 24 V (ac) ±10% 60 Hz 2 VA (98 VA max) Class 2 End Switch: 24 V (ac) 2 A Zone Output: 2 A per zone 4 A (max) total
Zone 4 Zone 5 Zone 6
Made in Canada tektra 1032-01
tN4 Wiring Center 315 Six Zone Valves Zone 2 C Vlv
Zone 3 C Vlv
A
Zone 4 C Vlv
Zone 5 C Vlv
Zone 6 C Vlv
Zone 6 R C tN4 W
Zone 1 Expansion End Switch Input Power R C tN4 C tN4 X X R C
End Switch
Zone 3
C R Zone 4
W
Power
Zone 2
W tN4
Zone 5 R C tN4
C R Zone 3
Zone 1
Zone 1 C Vlv
120 V (ac)
W tN4
W
End Switch
C R Zone 2
Use at least 167°F (75°C) conductors
tN4
R
L N
C tekmar 009 Transformer
Z1
Z2
Z3
Z4
Z5
Z6
Refer to Transformer Data Sheets for Maximum Allowable Loads tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
2 of 2
All specifications are subject to change without notice. Printed in Canada. C 315 - 01/11.