Submittal

Report 0 Downloads 383 Views
Submittal

C 315

tekmarNet® 4 Wiring Center 315

01/11 Zoning

Job ___________________________

Replaces: New

Contact_ _______________________

Designer_ ______________________

The tekmarNet 4 Wiring Center 315 is designed to provide a zoning solution for heating systems. It can be used in applications ranging from baseboard zones, to remote manifolds for radiant heating. This control energizes up to 6 zone valves. It is capable of providing power for up to 6 tekmarNet ®4, or stand alone thermostats, and energizing their respective 24 V (ac) zones, as well as providing an end switch closure to enable an external device such as a boiler. ®

Front View

Side View

Back View

1/2” Knock-out (x 4)

Zone 3

W tN4

C R Zone 4

W H8001

Input Power: 24 V (ac) ±10% 60 Hz 98 VA Max, Class 2 Control Load: 2 VA End Switch: 24 V (ac) 2 A Zone Output: 2 A per zone 4 A (max) total

Zone 4 Zone 5 Zone 6

Made in Canada tektra 1032-01

tN4 Wiring Center 315 Six Zone Valves Zone 1 C Vlv

Zone 2 C Vlv

Zone 3 C Vlv

A

Zone 4 C Vlv

Zone 5 C Vlv

Zone 6 C Vlv

Zone 6 R C tN4 W

End Switch

W

Zone 2

Zone 5 R C tN4

C R Zone 3

Power

Zone 1 Expansion End Switch Input Power R C tN4 C tN4 X X R C

7/8” (22 mm)

W tN4

W

5–1/2” (140 mm)

C R Zone 2

Zone 1

Use at least 167°F (75°C) conductors

tN4

CL 1–1/8” (30 mm) 5–1/2” (140 mm)

2–1/4” (57 mm)

1/2” x 5/8” (12 mm x 16 mm) Knock-out (x 4)

Ø 1/8” (3 mm)

7/8” x 1/2” (23 mm x 12 mm) Knock-out (x 4)

Specifications------------------------------------------------------ Features--------------------------tN4 Wiring Center 315 Six Zone Valves Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Zone valve load End switch relay Warranty

D315, Q315 Microprocessor control. This is not a safety (limit) control 1.4 lb. (630 g) 5.5” H x 5.5” W x 2.25” D (140 x 140 x 57 mm) Blue PC+ABS plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Noncondensing 24 V (ac) ±10%, 60 Hz, 98 VA, Class 2 24 V (ac) 2 A, maximum combined current (zones 1 to 4): 4 A 24 V (ac) 2 A Limited 3 Year (See D315 for full warranty)

• • • • • •

Six 24 V (ac) powered zone outputs For use with tekmarNet ® 4 thermostats tN4 expansion terminals Isolated end switch External diagnostic LEDs CSA C US Certified for use in USA and Canada

Special requirements

Designed for use with tekmarNet ®4 Thermostats. www.tekmarcontrols.com

 of 2

© 2011

C 315 - 01/11

Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram

315

Z1

Z2

tNt

tNt

Z3

tNt

tNt

Z4

tNt

Z5

tNt

tekmarNet® 4 Thermostats

Z6

tekmarNet® 4 Thermostats

Sample Electrical diagram Legend V1 = Balancing valve Z1 = Zone 1 Z2 = Zone 2 Z3 = Zone 3 Z4 = Zone 4 Z5 = Zone 5 Z6 = Zone 6 End Switch = Provides boiler demand on reset control (e.g. tekmar Boiler Control 260)

W H8001

Input Power: 24 V (ac) ±10% 60 Hz 2 VA (98 VA max) Class 2 End Switch: 24 V (ac) 2 A Zone Output: 2 A per zone 4 A (max) total

Zone 4 Zone 5 Zone 6

Made in Canada tektra 1032-01

tN4 Wiring Center 315 Six Zone Valves Zone 2 C Vlv

Zone 3 C Vlv

A

Zone 4 C Vlv

Zone 5 C Vlv

Zone 6 C Vlv

Zone 6 R C tN4 W

Zone 1 Expansion End Switch Input Power R C tN4 C tN4 X X R C

End Switch

Zone 3

C R Zone 4

W

Power

Zone 2

W tN4

Zone 5 R C tN4

C R Zone 3

Zone 1

Zone 1 C Vlv

120 V (ac)

W tN4

W

End Switch

C R Zone 2

Use at least 167°F (75°C) conductors

tN4

R

L N

C tekmar 009 Transformer

Z1

Z2

Z3

Z4

Z5

Z6

Refer to Transformer Data Sheets for Maximum Allowable Loads tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.

2 of 2

All specifications are subject to change without notice. Printed in Canada. C 315 - 01/11.