C 510
Submittal Programmable Thermostat 510
02/12 Zoning
Job __________________________
Replaces: 01/11
Contact _______________________
Designer ______________________
The Programmable Thermostat 510 is a micro-processor based control designed to operate mechanical equipment to deliver heat to a single zone within a hydronic heating system. It can be used with any terminal unit type, including radiant floor, baseboard, and fan coils. This product maintains very accurate and even air temperature with Pulse Width Modulation and Auto Cycling. It is capable of controlling a zone valve or zone pump directly or through a tekmarNet ® 4 Wiring Center or Zone Manager to maintain air temperature and 2 auxiliary temperatures. These temperatures could be floor or remote air.
Front View
Side View
Mounting Base 5/8” (17 mm)
7/8” (23 mm) Wire Access
2–7/8” (73 mm)
1/4” (7 mm)
2–7/8” (73 mm)
13/16” (21 mm)
1–3/8” (36 mm)
Specifications --------------------------------------------------------------------------------------- Energy Saving Features -----------• Programmable Setback Schedule
Programmable Thermostat 510 One Stage Heat Literature Control Packaged weight Dimensions Enclosure Approvals Ambient conditions Power supply Relays Sensors –Included –Optional Warranty
D510, U510. C510 Microprocessor control. This is not a safety (limit) control 0.5 lb. (230 g) 2-7/8” H x 2-7/8” W x 13/16” D (73 x 73 x 21 mm) White PVC plastic, NEMA type 1 CSA C US, meets class B: ICES & FCC Part 15 Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% Noncondensing 24 V (ac) ±10%, 60 Hz, 3 VA 24 V (ac) 2 A max, Class 2 NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892 None tekmar type #: 070, 072, 073, 076, 077, 079, 083, 084 Limited 3 Year (See D510 for full warranty)
Additional Features -----------------• Auto Heating Cycle • Pulse Width Modulation • CSA C US Approved for use in USA and Canada • Freeze Protection • 2 auxiliary sensor inputs • Slab max. and min. settings with installed slab sensor
SPECIAL REQUIREMENTS N/A www.tekmarcontrols.com
1 of 2
© 2012
C 510 - 02/12
Sample Application Drawing Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarcontrols.com. Sample Mechanical diagram
510
Optional Zone Manager or Wiring Center
316
S1
Sample Electrical diagram Legend
2 3 4 C Com S1
938-01
510
US C 24 V ± 10% 60 Hz 3 VA 24 V (ac) 2 A
Switch Settings: Installer/User
Power: Relay: Class 2
No Power
1 R
One Stage Heat
Programmable Thermostat 510
6 7 Heat
Made in Canada Meets Class B: Canadian ICES FCC Part 15
S1 = Slab Sensor
5 S2
or S1 tN4
C
R
W
or Indoor Sensor
Outdoor Sensor
Wiring Center or Zone Manager
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Office: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.com Product design, software and literature are Copyright © 2012 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
2 of 2
All specifications are subject to change without notice. Printed in Canada. C 510 - 02/12.