Flat Face Plate can be adjusted for right or left beveled edge doors. Radius Weather Strip is optional.
CL
"A"
AVAILABLE FACEPLATES
-.00
RADIUS
1.587 40.3
CL
BEVEL
RADIUS WEATHER STRIP
+.015 1.010 - .000 +0.4 25.7 0
CL 1.437 36.5
6.38 162
6.81 173
5.80 147.3
HOW BACKSET IS MEASURED 2.769 70.3
FOR OPTIMUM LOCK PERFORMANCE, THE GAP BETWEEN THE DOOR AND FRAME MUST MEET INDUSTRY STANDARDS OF AN 1/8"
(Must use a Face Plate for installation)
.182 [20.32]
Turning Key / Handle / Paddle DOES NOT pull Main Latch Assy.
.06 [1.5]
.611 [15.52]
CAM TOLERANCE: ±.005 ( ±.13 )
4300 SERIES ELECTRIFIED DEADLATCH 80-0180-421
Rev. D
2x #10-32 UNC-2B
Adjustable Mounting Tube Bracket may be removed for mounting on bridges, tabs, or either methods.
4581 FRONT VIEW
1.437 [36.5] 2.769 [70.3]
CL
CL .570 14.5
Adams Rite Manufacturing Co. 260 Santa Fe Street, Pomona, CA 91767 Phone: 909-632-2300 Fax: 909-632-2369 www.adamsrite.com
CL
4.635 CL 117.7
R.120 [3.0]
CYLINDER CL
CYLINDER CL
5.375 136.5
Press Aux Latch to secure Main Latch. Turn key, apply voltage, or operate Paddle/Handle to unlock Main Latch. As door opens, Main Latch pivots and collapses.
R.156 [3.96] TYP.
INSTALLATION
DOOR CL TO JAMB EDGE
OPERATION INSTRUCTION
.42 10.6
6.38 162.1
+.005
6.885 -.000 [174.9] +.38
FLAT
ECN:11899
4581 Cam Plug Assy. (included with 4300)
Drill and c'sk for #10-32 X 1/2" Flat Head Machine Screws
PRODUCT MUST BE INSTALLED ACCORDING TO ALL APPLICABLE BUILDING AND LIFE SAFETY CODES
SOLENOID AVAILABLE VOLTAGES 12V DC CONTINUOUS DUTY, 24V DC CONTINUOUS DUTY.
120V AC LINE VOLTAGE
4603 2-AMP RECTIFIER
MONITORED DEADLATCH CONTAINS AN INTERNALLY MOUNTED SWITCH. THIS SWITCH IS ACTIVATED WHEN THE DOOR IS IN CLOSE POSITION. ALL UNUSED LEADS FROM THE MONITOR SWITCH MUST BE INSULATED.
WHITE (+) 4300 ELECTRIFIED DEADLATCH
Common contact Normally Open contact (N.O.) Normally Closed contact (N.C.) Maximum switching current
RED 4605 / 4606 -24V AC 40 VA TRANSFORMER
BLACK (-)
BLUE
Black 24V DC
Red
Screwdriver
Fig. 6 Adams Rite Manufacturing Co. 260 Santa Fe Street, Pomona, CA 91767 Phone: 909-632-2300 Fax: 909-632-2369 www.adamsrite.com
WIRES BUNDLE
4300 SERIES ELECTRIFIED DEADLATCH 80-0180-421 Rev. D
ECN: 11899
Access Control System
White
4300 SERIES ELECTRIFIED DEADLATCH
Fig. 7
Black White Red 0.1 Amps @ 125 VAC
EXAMPLE WIRING DIAGRAM WITH N.O. MONITORING
ORANGE
12V DC
-
VOLTAGE ADAPTOR CABLE
- LOOP THE WIRES BUNDLE FROM 4300 ELECTRIFIED 'S SOLENOID UNDER AND AROUND ITS HOUSING AS SHOWN (Fig.7). - EXTEND THE WIRES RUN FROM THE POWER SOURCE AND THROUGH THE STILE PREPARATION. - CONNECT THE WIRE TO THE VOLTAGE ADAPTOR CABLE. - ATTACH VOLTAGE ADAPTOR CABLE TO 4300 WIRES BUNDLE AS SHOWN.
PRODUCT MUST BE INSTALLED ACCORDING TO ALL APPLICABLE BUILDING AND LIFE SAFETY CODES
X
4300 MONITOR
Black = Common White = N.O. contact (Dry) Red = N.C. contact (Dry) Unused wires must be cut such that no exposed wire will touch any metallic surface