PLK Wall MOUNT 1 , 2, 3-Lamp T5, T5HO, T8, Direct/Indirect Distribution Project Information Project Name
Type
Catalog No.
Date
Construction —Housing lengths of 4', 8', or 12' lengths —Mounting points maintain convenient, predictable locations.
Features • • • • • • • • • • • • •
Rectilinear wall mount Up to three T8, T5, or T5HO lamps in cross section Direct/Indirect distribution Heavy 20-gauge steel Symmetric distribution Controls compatible Attractive cable/bracket support mount Wide selection of flush or regressed shielding media Decorative perforated, slotted, or patterned strips on either side of shielding for added visual interest Integral small case ballasting Control compatible for daylight harvesting, occupancy sensors, or dimming Low profile, adjustable cable mount hanging system Office and school applications
—The exact shape of the housing is maintained by the use of a patented inner die cast plate at each fixture end (Patent# 6,796,676 B2) throughout the run to prevent snaking. The housing is designed to wrap around the plate and secures on top with concealed screws to ensure housing tolerances are consistent. Finish Housing and all painted parts are treated with a multi-stage phosphate prior to finish. Parts are then finished with a white powder coat for maximum consistent coverage and longevity. Other colors may be specified; refer to Color Selection Guide or contact your local Alera Lighting representative. Shielding Plank Wall Mount includes both direct and indirect lighting elements. Shielding for the direct element may be selected as a:
Mounting Plank Wall Mount is designed for wall mount applications using wall brackets. Brackets are universal and secure to the die cast end plates using a screw connection. Aircraft cable support may be used in addition to the wall bracket mounting if desired for aesthetic and/ or additional load carrying capacity. Electrical connections are made from a standard 2" × 4" j-box; j-box and j-box covers by others. Labels and Electrical —All luminaires are built to UL1598 standards and bear the appropriate cUL or CSA labels. Damp location listed. —Quick connect plugs standard.
Name: Test #: Efficiency: LER:
PLK-2T8-PERF-WCB-E 13890 92% 80
—White cross baffle (WCB),
Shape and Dimensions
—Regressed perforated panel (RPF)
2"
—Flat perforated panel (FPF) —Opal acrylic (OA)
9⅞"
—Acrylic pattern 12 (A12)
Ordering Information
PLK — Model PLK Plank
4 8 12 —
Row Length 4' Single 8' Single 12' Single Indicate row length over 12' in 4' increments
Example: PLK-16-1T5-WM-WCB-EU-MW
—
—
LAMP TYPE AND PROFILE 1T5 One T5 Lamp 2T5 Two T5 Lamps 3T5 Three T5 Lamps 1T5HO One T5HO Lamp 2T5HO Two T5HO Lamps 3T5HO Three T5HO Lamps 1T8 One T8 Lamp 2T8 Two T8 Lamps 3T8 Three T8 Lamps
Note: Rows over 12' will be configured by Alera. Example: 16' will be (2) 8'. Alternate configurations: contact factory.
Blank 0/100 20/80 40/60 85/15 CLC
— Housing type Blank Solid (Std.) PFST Perforated Strip HSLT Horizontal Slot Strip VSLT Vertical Slot Strip
Distribution None 0% Uplight Reflector, 100% Downlight5, 6 20% Uplight Reflector, 80% Downlight5, 6 40% Uplight Reflector, 60% Downlight5, 6 85% Uplight Reflector, 15% Downlight5, 6 Center Lamp Cover A/V Mode5, 6
—
— MOUNTING Method WM Wall Mount WMC Wall Mount with Cable
WCB RPF FPF OA A12
shielding White Cross Baffle1 Regressed Perforated Flat Perforated Opal Acrylic Lens Pattern 12 .125" Thick Acrylic Lens
Includes .020 thick white overlay. Specify voltage. For additional, specify quantity before nomenclature (Example: 2EL120, EMC277). 3 Not available with all configurations; some limitations apply. Contact factory for details. 4 One extra feed drop per EMC/NLC. For through wiring, contact factory. 5 Dust cover not available when using optical distribution covers. 6 Ships separately. 1 2
Page 1/4 Rev. 06/17/13
— Voltage U 120V277V 120 120V 277 277V 347 347V
Ballast E Electronic, Instant Start (Std. for T8) EP Electronic, Programmed Start (Std. for T5 & T5HO, optional for T8) ED Electronic, Dimming (Must specify) ESD Electronic, Step Dimming Unless specified, Alera will use fewest ballasts possible.
—
Finish MW Matte White (Std.) ZT ZET Metallic Silver See Color Selection Guide for other colors.
Options DC Dust Cover (T8 only) LR Left/Right Switching (2-Lamp only) IBOB Inboard/Outboard Switching (3-Lamp only) EL One Emergency Battery Pack 2, 3 EMC One Emergency Circuit2, 3, 4 NLC Night Light Circuit2, 3, 4 GLR Fast Blow Fuse GMF Slow Blow Fuse
Protected by US Patent 6,796,676. Protected by Canada Patent 2,450,528. Specifications subject to change without notice.
© 2013 Alera Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Alera Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.aleralighting.com
Beams / PLK WM
PLK Wall MOUNT 1 , 2, 3-Lamp T5, T5HO, T8, Direct/Indirect Distribution Cross section
8⅜"
8⅜"
2"
8⅜"
2"
⅜"
2"
⅜"
9⅞" 10⅛" 1T8 Lamp
⅜"
9⅞" 10⅛" 2T8 Lamps
9⅞" 10⅛" 3T8 Lamps
Photometric Data
Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet
PLK-1T8-WCB-E Plank Architectural Beam 9.75 × 48 1-Lamp with Gloss White Cross Baffle and Opal Overlay REL-1P32-SC 0.92 F32T8 2900 34 0º = 90 90º = 90 0º = 1.03 90º = 1.25 Length: 3.67 Width: 0.25 Height: 0.00
Avg. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) 0 30 40 45 50 55 60 65 70 75 80 85
0.0 22.5 45.0 67.5 90.0
3344 2587 2205 1974 1697 1493 1408 1332 1269 1224 1216 1212
3344 2642 2297 2074 1843 1554 1455 1360 1269 1269 1216 1077
3344 2831 2542 2373 2190 1964 1713 1555 1441 1315 1216 808
3344 3089 2894 2771 2628 2434 2135 1638 1338 1179 1013 673
3344 3265 3155 3069 2957 2741 2276 1555 1166 1133 946 673
Zonal Lumen Summary Zone
0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180
Lumens % Lamp % Fixt. 207 327 529 620 774 1138 1767 2179 2799
7.1 11.3 18.2 21.4 26.7 39.2 60.9 75.1 96.5
7.4 11.7 18.9 22.1 27.7 40.6 63.1 77.9 100.0
RCR
Luminaire
Angle
Luminaire Data Test 14038
RC RW 1 2 3 4 5 6 7 8 9 10
70 89 81 74 67 62 57 52 48 45 42
80 50 30 85 81 74 69 65 59 58 51 51 44 46 38 41 34 37 30 34 27 31 24
10 78 64 53 45 38 33 29 25 22 20
70 78 71 65 60 55 50 46 43 40 37
70 50 30 75 72 66 61 58 53 51 45 46 40 41 35 37 31 33 27 30 24 28 22
10 70 57 48 41 35 30 26 23 20 18
50 58 51 45 40 35 32 29 26 24 22
50 30 56 48 41 36 31 27 24 22 20 18
10 54 45 38 32 28 24 21 19 17 15
Indoor Candela Plot 0 0 18 16 14 12 10 9 8 7 7 6
180 165 600
150
120 300 105 90
RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance
75
Energy Data Total Luminaire Efficiency Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens
135
300
96.5% 76 Yes-VDT Intensive Use $3.16 based on 3000 hrs. and $0.08 per KWH
60
600 0 0.0
45 15 30 Horiz 0-180 90.0 45.0 Test Date 9/16/05
Photometric Data
Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet
PLK-2T8-WCB-E Plank Architectural Beam 9.75 × 48 2-Lamp with Gloss White Center Louver and Side Reflectors REL-2P32-SC 0.88 F32T8 2900 63 0º = 90 90º = 90 0º = 1.03 90º = 1.23 Length: 3.67 Width: 0.25 Height: 0.00
Avg. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) 0 30 40 45 50 55 60 65 70 75 80 85
0.0 22.5 45.0 67.5 90.0
8095 6259 5314 4745 4107 3579 3402 3220 3053 2992 3040 3365
8095 6435 5544 5011 4435 3784 3473 3276 3121 3128 3175 3365
8095 6882 6126 5691 5183 4643 4059 3692 3499 3309 3243 3365
8095 7451 6876 6504 6059 5543 4974 4331 3636 3309 3243 3231
8095 7762 7366 7051 6662 6095 5467 4608 3567 3264 3243 3231
Zonal Lumen Summary Zone
0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180
Lumens % Lamp % Fixt. 502 790 1266 1506 1211 1907 3221 4108 5613
8.7 13.6 21.8 26.0 20.9 32.9 55.5 70.8 96.8
8.9 14.1 22.6 26.8 21.6 34.0 57.4 73.2 100.0
RCR
Luminaire
Angle
Luminaire Data Test 14014
RC RW 1 2 3 4 5 6 7 8 9 10
70 90 82 75 68 63 58 53 49 46 43
80 50 30 86 82 75 70 66 59 59 51 52 45 47 39 42 35 38 31 35 28 32 25
10 79 65 54 46 39 34 30 26 23 20
70 80 73 67 61 56 51 48 44 41 38
70 50 30 77 74 67 63 59 54 53 46 47 41 42 36 38 32 34 28 31 25 29 23
10 71 59 49 42 36 31 27 24 21 19
50 60 53 47 41 37 33 30 27 25 23
50 30 58 49 43 37 33 29 26 23 21 19
10 56 47 39 34 29 25 22 20 17 16
Indoor Candela Plot 0 0 22 19 16 14 12 11 10 9 8 7
180 165 1100
120
105 90 75
Energy Data
550
96.8% 78 Yes-VDT Intensive Use $3.08 based on 3000 hrs. and $0.08 per KWH
135
550
RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance
Total Luminaire Efficiency Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens
150
60
1100 0 0.0
15 30 45 Horiz 0-180 90.0 45.0 Test Date 9/18/07
Page 2/4 Rev. 06/17/13 © 2013 Alera Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Alera Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.aleralighting.com
Beams / PLK WM
PLK Wall MOUNT 1 , 2, 3-Lamp T5, T5HO, T8, Direct/Indirect Distribution Photometric Data
Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet
PLK-3T8-WCB-E Plank Architectural Beam 9.75 × 48 3-Lamp with Gloss White Center Louver and Side Reflectors REL-3P32-SC 0.88 F32T8 2900 88 0º = 90 90º = 90 0º = 1.02 90º = 1.17 Length: 3.67 Width: 0.25 Height: 0.00
Avg. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) 0 30 40 45 50 55 60 65 70 75 80 85
0.0 22.5 45.0 67.5 90.0
12424 9523 8071 7201 6187 5420 5092 4802 4494 4306 4256 4308
12424 9632 8239 7433 6516 5584 5162 4830 4528 4442 4256 3904
12424 10079 8852 8179 7447 6668 5889 5385 5077 4669 4256 3500
12424 10770 9801 9291 8797 8243 7579 6829 5934 5031 4459 3500
12424 11230 10537 10187 9819 9368 8799 7967 6860 5394 4662 3500
Zonal Lumen Summary Zone
0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180
Lumens % Lamp % Fixt. 752 1173 1871 2224 1518 2517 4463 5794 8018
8.6 13.5 21.5 25.6 17.4 28.9 51.3 66.6 92.2
9.4 14.6 23.3 27.7 18.9 31.4 55.7 72.3 100.0
RCR
Luminaire
Angle
Luminaire Data Test 14017
RC RW 1 2 3 4 5 6 7 8 9 10
70 86 78 71 65 60 55 51 47 44 41
80 50 30 82 79 72 66 63 57 56 49 50 43 45 38 40 33 36 30 33 27 30 24
10 76 62 52 44 38 32 28 25 22 20
70 77 70 64 58 53 49 45 42 39 37
70 50 30 73 71 64 60 57 51 50 45 45 39 40 34 36 30 33 27 30 24 27 22
10 68 56 47 40 34 30 26 23 20 18
50 57 51 45 40 36 32 29 26 24 22
50 30 56 48 41 36 31 28 25 22 20 18
10 54 45 38 32 28 24 21 19 17 15
Indoor Candela Plot 0 0 22 19 16 14 12 11 10 9 8 7
180
165
150
120 850 105 90
RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance
75
Energy Data Total Luminaire Efficiency Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens
135
1700
850
92.2% 80 Yes-VDT Normal Use $3.00 based on 3000 hrs. and $0.08 per KWH
60
1700 0 0.0
15 30 45 Horiz 0-180 90.0 45.0 Test Date 8/11/05
Photometric Data
Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet
PLK-1T5HO-WCB-EP Plank Architectural Beam 9.75 × 48 1-Lamp with Gloss White Center Louver and Opal Overlay ICN2S5490C 1.02 F54T5HO 4450 62 0º = 90 90º = 90 0º = 1.03 90º = 1.25 Length: 3.67 Width: 0.25 Height: 0.00
Avg. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) 0 30 40 45 50 55 60 65 70 75 80 85
0.0 22.5 45.0 67.5 90.0
4540 3509 2971 2671 2318 2045 1924 1832 1749 1677 1757 1750
4540 3603 3124 2837 2519 2168 1994 1888 1818 1813 1757 1615
4540 3888 3492 3252 2975 2679 2370 2165 2024 1904 1824 1615
4540 4240 3967 3750 3504 3129 2651 2249 1989 1904 1757 1481
4540 4430 4242 4048 3778 3334 2745 2221 1887 1813 1757 1481
Zonal Lumen Summary Zone
0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180
Lumens % Lamp % Fixt. 282 446 716 847 1225 1793 2785 3434 4281
6.3 10.0 16.1 19.0 27.5 40.3 62.6 77.2 96.2
6.6 10.4 16.7 19.8 28.6 41.9 65.0 80.2 100.0
RCR
Luminaire
Angle
Luminaire Data Test 14020
RC RW 1 2 3 4 5 6 7 8 9 10
70 88 80 73 67 61 56 52 48 44 41
80 50 30 84 80 73 68 64 58 57 50 51 43 45 38 41 33 37 30 33 27 30 24
10 77 63 53 44 38 33 28 25 22 20
70 77 70 64 59 54 49 46 42 39 37
70 50 30 74 71 65 60 57 52 51 45 45 39 40 34 36 30 33 27 30 24 27 22
10 69 57 47 40 34 30 26 23 20 18
50 56 49 44 39 35 31 28 25 23 21
50 30 54 46 40 35 30 27 24 21 19 17
10 53 44 37 31 27 23 20 18 16 14
Indoor Candela Plot 0 0 16 14 12 10 9 8 7 7 6 5
180
165
135
120 400 105 90
RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance
75
Energy Data Total Luminaire Efficiency Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens
150
800
400
96.2% 70 Yes-VDT Intensive Use $3.43 based on 3000 hrs. and $0.08 per KWH
60
800 0 0.0
15 30 45 Horiz 0-180 90.0 45.0 Test Date 8/15/05
Page 3/4 Rev. 06/17/13 © 2013 Alera Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Alera Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.aleralighting.com
Beams / PLK WM
PLK Wall MOUNT 1 , 2, 3-Lamp T5, T5HO, T8, Direct/Indirect Distribution Photometric Data
Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet
PLK-2T5HO-WCB-EP Plank Architectural Beam 9.75 × 48 2-Lamp with Gloss White Center Louver and Opal Overlay ICN2S5490C 1.00 F54T5HO 4450 121 0º = 90 90º = 90 0º = 1.02 90º = 1.21 Length: 3.67 Width: 0.25 Height: 0.00
Avg. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) 0 30 40 45 50 55 60 65 70 75 80 85
0.0 22.5 45.0 67.5 90.0
9890 7573 6417 5724 4964 4377 4153 3942 3739 3626 3716 3904
9890 7749 6647 6023 5275 4541 4200 3970 3773 3717 3581 3231
9890 8263 7275 6686 6078 5400 4834 4469 4288 3944 3783 3096
9890 8900 8071 7549 7063 6484 5913 5274 4494 4034 3716 2692
9890 9279 8592 8179 7720 7220 6617 5746 4596 4125 3783 2827
Zonal Lumen Summary Zone
0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180
Lumens % Lamp % Fixt. 608 952 1514 1798 2078 3203 5222 6569 8366
6.8 10.7 17.0 20.2 23.4 36.0 58.7 73.8 94.0
7.3 11.4 18.1 21.5 24.8 38.3 62.4 78.5 100.0
RCR
Luminaire
Angle
Luminaire Data Test 14021
RC RW 1 2 3 4 5 6 7 8 9 10
70 86 78 72 66 60 55 51 47 44 41
80 50 30 82 79 72 67 63 57 56 49 50 43 45 37 40 33 36 29 33 26 30 24
10 76 62 52 44 37 32 28 25 22 19
70 76 69 63 58 53 49 45 42 39 36
70 50 30 73 70 64 60 56 51 50 44 44 38 40 34 36 30 32 27 30 24 27 21
10 68 56 47 39 34 29 25 22 20 18
50 56 49 43 38 34 31 28 25 23 21
50 30 54 46 40 34 30 27 24 21 19 17
10 52 43 37 31 27 23 20 18 16 14
Indoor Candela Plot 0 0 17 15 13 11 10 9 8 7 6 6
180
165
150
120 850 105 90
RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance
75
Energy Data Total Luminaire Efficiency Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens
135
1700
850
94.0% 69 Yes-VDT Normal Use $3.48 based on 3000 hrs. and $0.08 per KWH
60
1700 0 0.0
15 30 45 Horiz 0-180 90.0 45.0 Test Date 8/17/05
Photometric Data
Ballast Ballast Factor Lamp Lumens per Lamp Watts Shielding Angle Spacing Criterion Luminous Opening in Feet
PLK-3T5HO-WCB-EP Plank Architectural Beam 9.75 × 48 3-Lamp with Gloss White Center Louver and Opal Overlay ICN-4S5490C-2LS 1.00 F54T5HO 4450 183 0º = 90 90º = 90 0º = 1.02 90º = 1.16 Length: 3.67 Width: 0.25 Height: 0.00
Avg. Luminance (Candela/Sq. M.) Coefficients of Utilization (%) 0 30 40 45 50 55 60 65 70 75 80 85
0.0 22.5 45.0 67.5 90.0
16049 12260 10368 9225 7958 6995 6617 6274 5900 5757 5810 5923
16049 12409 10583 9540 8396 7220 6711 6302 5900 5893 5743 5115
16049 13005 11425 10585 9673 8693 7743 7162 6757 6255 5945 4846
16049 13736 12558 11879 11225 10431 9479 8467 7306 6391 5608 4577
16049 14400 13554 13074 12557 11863 10864 9716 8198 6845 5878 4308
Zonal Lumen Summary Zone
0-30 0-40 0-60 0-90 90-120 90-130 90-150 90-180 0-180
Lumens % Lamp % Fixt. 968 1510 2405 2861 2725 4341 7284 9259 12120
7.3 11.3 18.0 21.4 20.4 32.5 54.8 69.4 90.8
8.0 12.5 19.8 23.6 22.5 35.8 60.1 76.4 100.0
RCR
Luminaire
Angle
Luminaire Data Test 14024
RC RW 1 2 3 4 5 6 7 8 9 10
70 84 76 70 64 58 54 50 46 43 40
80 50 30 80 77 70 65 62 55 54 48 48 41 43 36 39 32 35 29 32 26 29 23
10 74 60 50 43 36 31 27 24 21 19
70 74 68 62 56 52 48 44 41 38 35
70 50 30 71 68 62 58 55 50 49 43 43 37 39 33 35 29 32 26 29 23 26 21
10 66 54 45 39 33 29 25 22 19 17
50 55 48 43 38 34 30 27 25 23 21
50 30 53 45 39 34 30 26 23 21 19 17
10 51 43 36 31 26 23 20 18 16 14
Indoor Candela Plot 0 0 18 16 13 12 10 9 8 7 7 6
180
165
150
135
2600 120 1300 105 90
RCR = Room Cavity Ratio RC = Effective Ceiling Cavity Reflectance RW = Wall Reflectance
75
Energy Data Total Luminaire Efficiency Luminaire Efficacy Rating (LER) ANSI/IESNA RP-1-2004 Compliance Comparative Yearly Lighting Energy Cost per 1000 Lumens
90.8% 66 Noncompliant $3.64 based on 3000 hrs. and $0.08 per KWH
1300
60
2600 0 0.0
15 30 45 Horiz 0-180 90.0 45.0 Test Date 9/6/05
Page 4/4 Rev. 06/17/13 © 2013 Alera Lighting, a division of Hubbell Lighting, Inc. Because of continuing product improvement programs, Alera Lighting reserves the right to change specifications without notice. 701 Millennium Blvd. Greenville, SC 29607 / Tel 864.678.1000 / Website www.aleralighting.com
Beams / PLK WM