Approved
Fabrication and/or installation may be undertaken. Approval does not authorize changes to the contract sum or contract time.
Approved as Corrected Revise and Resubmit
SUBMITTAL REVIEW COMMENTS PROJECT PROJECT NO DATE SUBMITTAL SUBMITTAL NO REVIEWER
Olathe West High School- Olathe, KS 1250002050 09/04/2015 Dust Collector Resubmittal H007R1 Chris Greer
Fabrication and/or installation may not be undertaken. In resubmitting, limit corrections to items marked.
Rejected No Action Taken
Submittal either not required for this item or provided for information only. Contract requirements should be followed in all cases. Review/approval neither extends nor alters any contractual obligations of the Engineer or Contractor. Checking of submittals is only for general conformance with the design concept of the project and general compliance with the information given in the contract documents. Any action shown is subject to the general requirements of the plans and specifications. Contractor is responsible for dimensions, quantities, and coordination between trades and for coordinating approved items and accepted alternates.
HENDERSON ENGINEERS, INC.
ACTION CODES
1
2
3
4
5
6
Approved
Approved as Corrected
Revise & Resubmit Items Noted
Rejected
Not Reviewed
For Information Only
(Action Item Codes 1, 2, 5 or 6 are not to be resubmitted.)
COMMENT #
ACTION CODE
1
6
DESCRIPTION
COMMENTS
Unit Configuration
Configuration of submitted equipment differs from scheduled unit. Scheduled unit inlet was rear single duct connection. Discharge configuration of submitted equipment appears to be top (scheduled equipment was horizontal and rotated). Contractor responsible for coordinating modified duct connection requirements.
Page 2 of 2
Note: HEI’s processing of these submittals does not relieve other members of the design and construction team from reviewing submittals for coordination, compliance and performance or reviewing submittals as outlined in the contract documents or both.
Submittal #680.1 Project: 1-07-0532 - Olathe West High School 2200 W. Santa Fe Olathe, Kansas 66061 Phone: 816-960-1111 Fax: 816-960-1182
McCownGordon 422 Admiral Boulevard Kansas City, Missouri 64106 Phone: (816) 960-1111 Fax: (816) 960-1182
Revised Dust Collector SPEC SECTION:
CREATED BY:
Gina Peterman(McCownGordon Construction, LLC)
STATUS:
In Review
DATE CREATED:
08/03/2015
ISSUE DATE:
09/02/2015
REVISION:
1
RESPONSIBLE CONTRACTOR:
MidStates Heating and Cooling
RECEIVED FROM:
Jason Larsen
RECEIVED DATE: //
SUBMIT BY:
//
FINAL DUE DATE: 09/16/2015
LOCATION:
TYPE:
Shop Drawing
COST CODE:
APPROVERS:
Lori Rinehart (Henderson Engineers, Inc.)
BALL IN COURT: Lori Rinehart (Henderson Engineers, Inc.) DISTRIBUTION: Gregory Schiller (Hollis + Miller Architects, Inc.), Shayna Miller (McCownGordon Construction, LLC) DESCRIPTION: Comment made by the supplier: 1). We do not recommend the use of a VFD with our dust collector even for balancing. A VFD would allow the ability to change the system velocity below the minimum recommendation which in turn can cause a duct blockage. Please review the attached Revised Dust Collector Shop Drawings from MidStates. Let us know if you have any questions ATTACHMENTS: Revised Dust Collector - For Approval.pdf
SUBMITTAL WORKFLOW # 1
NAME Lori Rinehart
SUBMITTER/ APPROVER
SENT DATE
Approver
9/2/2015
DUE DATE
RETURNED RESPONSE DATE
ATTACHMENTS
COMMENTS
Pending
BY
McCownGordon
DATE
COPIES TO
Page 1 of 1
Printed On: 09/02/2015 02:19 PM
RESUBMITTAL
680-1
07-532
Project _______________ Submittal No. ___________________
REVIEWED ONLY
PROJECT: LOCATION: ARCH: ENG: SUB-CONT: DATE:
Manufacturer DONALDSON TORIT
OLATHE WEST HIGH SCHOOL OLATHE, KANSAS HOLLIS + MILLER ARCHITECTS HENDERSON ENGINEERS MID STATES SEPTEMBER 1, 2015
Product Dust Collectors & AfterFilters
Contractor's review is for general compliance with the information provided in the Contract Documents and for general conformance with the design concept of the project. Any action noted herein is subject to the requirements set forth in the Contract Documents Subcontractor/ Suppliers responsible for all dimensions which shall be confirmed at the jobsite; all fabrication processes and techniques of construction; the coordination of Subcontractor's work with that of all other trades, and the performance of Subcontractor's work in accordance with the Contract Documents
McCownGordon Construction gpeterman
2:16:01 PM
09/02/2015
Specification Section N/A
Dust Collector is being resubmitted with HP’s equal to those scheduled. Each dust collector will have inlet connections located on the rear of the unit, one for each hopper.. Barrels will be provided as part of the dust collector package. Dust Collectors 1). We do not recommend the use of a VFD with our dust collector even for balancing. A VFD would allow the ability to change the system velocity below the minimum recommendation which in turn can cause a duct blockage.
PROJECT: LOCATION: SUB-CONT: DATE:
OLATHE WEST HIGH SCHOOL OLATHE, KANSAS MID STATES SEPTEMBER 1, 2015
SUBMITTED BY:
KEVIN FARRELL TRIANGLE SALES, INC P.O. BOX 14628 LENEXA, KS 66285 (913) 541-1800 (913) 541-0011 FAX
[email protected] DUST COLLECTORS & AFTER-FILTERS Specification-N/A DUST COLLECTORS Donaldson Torit model UMA-450 Unimaster, self-contained shaker type dust collector furnished as 16 ga. steel housing with 12" dia. inlet on rear of unit (one per hopper), integral fan with 460/60/3 TEFC motor and 1/3 hp shaker motor. Each dust collector also furnished with integral silencer. Controller includes fan control, timer for shaker motor and NEMA 12 enclosure with standard clean pushbuttons. Furnished with barrel top adapters with flex connections, 55 gal barrels and magnehelic gage. Tag DC-1 -Wood shop Qty. 1 - UMA450 with 10hp 460/60/3 TEFC motor Duty 4000 CFM @ 8.25" s.p. with 450 square ft of filter media Tag DC-2 -Sculpture Qty. 1 - UMA 450with 15hp 460/60/3 TEFC motor Duty 4600 CFM @ 9.0" s.p. with 450 square ft of filter media NOTE: VFDs are not recommended by the factory and are not included as these allow the system to be turned down below recommended velocity and cause duct blockages. Secondary filters will be furnished as Donaldson Trit Auto Lock side access fitter housings, 16 ga. galvanized construction. Housings will be furnished with MERV 14 (ASHRAE 9590) filters. Tag DC-1 -Wood shop - 4,000 CFM Qty. 1 - Housing - 2 filters wide by 1 filter tall (47.24" W x 26.74" Tall x 18" Depth O.D.) with qty 2 filters Tag DC-2 -Sculpture - 4,600 CFM Qty. 1 - Housing - 3 filters wide by 1 filter Tall (70.86" W x 26.74" Tall x 18" Depth O.D.) with qty 3 filters
PROJECT: LOCATION: SUB-CONT: DATE:
OLATHE WEST HIGH SCHOOL OLATHE, KANSAS MID STATES SEPTEMBER 1, 2015
SUBMITTED BY:
KEVIN FARRELL TRIANGLE SALES, INC P.O. BOX 14628 LENEXA, KS 66285 (913) 541-1800 (913) 541-0011 FAX
[email protected] Tag: Sculpture
Tag: Wood Shop