SUBMITTAL REVIEW COMMENTS FOR

SPLIT SYSTEM SUBMITTAL BLAKESLEE PROJECT: Pocono Medical Center Blakeslee DATE: June 28, 2016 DATE RECEIVED: June 22, 2016 DATE PROCESSED: June 27, 2016 1.

ITEM Split System

COMMENTS Make Corrections Noted. 1. Provide with wind baffle accessory. 2. Provide with one year parts warranty.

This submittal was not reviewed for coordination with other systems to be installed. It is the contractor’s responsibility to coordinate the installation with all other trade contractor’s work. The review is for basic compliance with the design intent. It does not release the contractor from providing all specific requirements of the equipment and installation that may not have been listed on the shop drawing but were called for on the drawings or in the specifications. Contractor shall be responsible for dimensions that are to be confirmed at the job site for coordination in the ordering and assembly of equipment, for information that pertains solely to fabrication processes, or to techniques of construction, and for coordination of the work of all trades.

REVIEWED BY: Jared C. Ferri

STRUNK ALBERT ENGINEERING Z:\Pocono Medical Center Blakeslee & Tannersville MOB (PBT) 14215\CONSTRUCTION PHASE\Submittals\Mech\OUT\20169069 28 Split Systems (Blakeslee)\SRC9199Split System (Blakeslee).Doc

STRUNK ALBERT ENGINEERING 804 Seven Bridge Road • East Stroudsburg, PA 18301 570 421 2025 • mail@strunk albert.com • www.strunk albert.com Partners: David B. Strunk, P.E. and Kenneth R. Zimmerman, P.E.

DUAL TEMP CO., INC.

LETTER OF TRANSMITTAL

2050 South 12th Street Allentown, PA 18103 (610) 791-9100 (610) 791-9124 Fax

DATE: June 22, 2016

========================================================================= TO:

Allied Building Corporation 574 Main St, Ste. 200 Bethlehem, PA 18018 Attn: Ken Prutzman

RE: PMC Blakeslee Fit-Out

========================================================================== We are forwarding to you: Submittals

# of Copies

Plans

Specifications

Spec

Description

1

Split System

=========================================================================== These are being transmitted to you: X For Approval

For Your Use

Make Corrections Noted

As Requested

No Exceptions Taken

Release for Shipment

Record Purposes Only

Reviewed as Noted

Revise and Resubmit

Remarks:

Pam Keeley_______________ Construction Coordinator X X June 28, 2016

JCF

PKA-A12HA6 & PUY-A12NHA6 (-BS)

P-SERIES Job Name: PMC

12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM

Blakeslee

System Reference: ACU-1/

Date: 6/21/16

CU-1 Indoor Unit Blower Motor (ECM)

F.L.A.

0.33

Blower Motor Output

W

30 0.81 / 2 pt./h

SHF / Moisture Removal

Indoor Unit: PKA-A12HA6

Outdoor Unit Outdoor Unit: PUY-A12NHA6 (-BS)

UNIT OPTION: □□ Standard Model......................................................................PUY-A12NHA6 □□ Seacoast (BS) Model.......................................................PUY-A12NHA6-BS

DC INVERTER-driven Twin Rotary

Compressor Fan Motor (ECM)

F.L.A.

0.35

MOCP

A

15

ACCESSORIES:

Airflow Rate (Low-Mid-High)

Indoor Unit

Indoor (Cooling)

DRY

Outdoor

DRY

□□ Condensate Pump (BlueDiamond X87-711/721; 115/230V) □□ Condensate Pump (Sauermann SI30-115/230; 115/230V) □□ Disconnect Switch (TAZ-MS303) □□ Wireless Remote Controller (PAR-FL32MA-E) □□ Wireless Signal Receiver (PAR-FA32MA-E) Outdoor Unit

WET

Outdoor

*Allows operation to 0º F (-18º C).

□□ Advanced Wind Baffle (WB-SD1 and/or WB-RE1)** **Allows operation to -20º F (-29º C).

□□ Air Outlet Guide (PAC-SG58SG-E) □□ Wall Bracket (QSWB2000M-1)

Cooling

Outdoor (H x W x D)

Btu/h / W

48

11-5/8 x 35-3/8 x 9-13/16 (295 x 898 x 249) 23-5/8 x 31-1/2 x 11-13/16 + 7/8 (600 x 800 x 300 + 23)

Indoor

Lbs.(kg)

29 (13) 82 (37)

External Finish

12,000 / 1,190

* Rating Conditions per AHRI Standard: Cooling | Indoor: 80º F (27º C) DB / 67º F (19º C) WB Cooling | Outdoor: 95º F (35º C) DB / 75º F (24º C) WB

Capacity Range Btu/h

36-40-43

Net Weight

Outdoor

Rated Conditions (Capacity / Input)*

6,000 - 12,000

Operating Range Cooling

dB(A)

In.(mm)

SPECIFICATIONS:

Cooling

1,200

Indoor (H x W x D)

□□ Wireless Controller (MHK1) □□ Advanced Wired Controller (PAR-31MAA) □□ Simple Wired Controller (PAC-YT53CRAU) □□ M-NET Adapter (PAC-SF83MA-E) □□ Temperature Sensor (PAC-SE41TS)

290-335-380

External Dimensions

Controls

Cooling

CFM

Sound Pressure Level Indoor (Low-Mid-High)

□□ Wind Baffle (WB-PA1)*

320-370-425

Indoor

Munsell No. 1.0Y 9.2 / 0.2

Outdoor

Munsell No. 3Y 7.8 / 1.1

Refrigerant

R410A ; 2 lbs., 14 oz.

Refrigerant Piping (Flared) Liquid (High Pressure) Gas (Low Pressure)

-20º F to 115º F (-29º C to 46º C) DB**

**Applies only to systems utilizing Advanced Wind Baffle Kit. Equipment operation range without any additional accessories: 23º F to 115º F (-5º C to 46º C) DB. Equipment operation range with Standard Wind Baffle: 0º F to 115º F (-18º C to 46º C) DB. For operation below -20º F (-29º C) DB, please contact your Mitsubishi Electric representative.

In.(mm)

1/4 (6.35) 1/2 (12.7)

Maximim Total Refrigerant Pipe Length

Ft. (m)

165 (50)

Maximum Vertical Separation

Ft. (m)

100 (30)

AHRI Efficiency Ratings EER

10.1

SEER

15.2

Electrical Power Requirements

208 / 230V, 1-Phase, 60 Hz

Minimum Circuit Ampacity (MCA) Indoor / Outdoor

A

1 / 13

Specifications are subject to change without notice.

© 2015 Mitsubishi Electric US, Inc.

DIMENSIONS: PKA-A12HA6 & PUY-A12NHA6 (-BS) PKA-A12HA6

PUY-A12NHA6 (-BS)

NOTES: SEACOAST PROTECTION • External Outer Panel: Phosphate coating + Acrylic-Enamel coating • Fan Motor Support: Epoxy resinspace coating around (at edge face) Clearance the outdoor unit • Separator Assembly ; Valve Bed: Epoxy resin coating (at edge face) • Screws (used outer side): Zinc nickel coating 5μm + Polyvinylidene chloride coating

“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants..

1340 Satellite Boulevard. Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com

FORM# PKA-A12HA6 - PUY-A12NHA6 (-BS) - 201511 Specifications are subject to change without notice.

© 2015 Mitsubishi Electric US, Inc.

SUBMITTAL DATA: MHK1 REMOTE CONTROLLER KIT FOR M-SERIES AND P-SERIES Job Name:

Location:

Purchaser:

Engineer:

Submitted to:

For

System Designation:

Schedule No.:

Reference

Date: Approval

Construction

MHK1 REMOTE CONTROLLER KIT INCLUDES: MRCH1 REMOTE CONTROLLER • For use with P-Series NHA4 systems, SEZ-4/SUZ one-toone systems, SLZ/SUZ one-to-one systems, MXZ-B multi-zone systems, MSY/MSZ, and MFZ indoor units • Backlit, easy-to-read display • Supports both Fahrenheit and Celsius • User functions allow user to set: - On/Off - Operation modes cool,heat, drying, fan - Set temperature (separate dual set points for heat and cool) - Fan speed setting - Airflow direction • Day/Time display with a 12-hour clock • Filter sign display • Optimal start • Adjustable auto deadband • Space temperature offset adjustment • Display outside temperature and humidity (requires optional MOS1, sold separately) • Hold function • Temporary schedule override • Reset to factory default • Auto lock display • Timer Operation: - Daily Timer: On/Off times can be set up to 4 times per day in 15-minute increments. - Weekly Timer: On/Off times can be set up to 4 times per day of the week in 15-minute increments. Choice of 5-2 and 5-1-1 weekly schedules for heat, cool, auto (separate for each mode) - Auto-off Timer: Turns indoor unit Off at scheduled time up to 24 hours in advance • Room Temperature: Displays room temperature sensed either at the indoor unit or at the remote controller (default) • Set temperature range limits (dependent on the system connected):



Cooling from 50° to 99°F Heating from 40° to 90°F Auto from 50° to 90°F with dual temperature setting

• • • •

Diagnostics: Displays and records error codes No addressing required Can be integrated with other RedLINK™ devices Wiring: Connects using five-conductor cable from MIFH1 Wireless Receiver (cable included) to indoor unit; wireless RF from the MIFH1 Wireless Receiver to the MRCH1 Remote Controller • Dimensions: 3-9/16" H x 5-13/16" W x 1-1/2" D (147 x 38 x 91mm) • Uses two “AA” alkaline batteries (included) MIFH1 WIRELESS RECEIVER

• Mounts next to or near indoor units to allow MRCH1 Remote Controller operation of P-Series NHA4 systems, SEZ-4/SUZ oneto-one systems, SLZ/SUZ one-toone systems , MXZ-B multi-zone

systems, MSY/MSZ, and MFZ indoor units

• Dimensions: 6-7/16” H x 3-1/4” W x 1-5/16” D (164 x 82.5 x 34 mm) MRC1 CABLE • Connects MIFH1 Wireless Receiver to fivepin CN105 on indoor unit control board • Five-conductor wire with preterminated ends • Length: 6-1/2' (2 m)

OPTIONAL ACCESSORIES

□□ Portable Central Controller (MCCH1; for use with Wireless Remote Controller Kit MHK1)* □□ Outdoor Air Sensor (MOS1; for use with Wireless Remote Controller Kit MHK1)* *See Submittal for information on each option.

MIFH1 Wireless receiver r MOS1 Outside Air Sensor (Optional)

MRCH1 Remote controller

MCCH1 Portable central controller Mr.Slim Outdoor Unit

FORM# MHK1 - 201108 RedLINK is a trademark of Honeywell, Inc. © 2011 MITSUBISHI ELECTRIC & ELECTRONICS, INC.

3400 Lawrenceville Suwanee Rd Suwanee, GA 30024 Tele: 678-376-2900 • Fax: 800-889-9904 Toll Free: 800-433-4822 (#3) www.mehvac.com Specifications are subject to change without notice.

DPLS1 DRAIN PANEL LEVEL SENSOR / LEVEL CONTROL

DESIGNED FOR MFZ, MS, MSY/Z, SEZ, SLZ, PCA/PCFY, PDFY, PEA/PEAD, PKA/PKFY, PLA, PLKA/PLFY, PMFY, and PVFY Job Name: System Reference:

Date:

COMPONENTS

GENERAL FEATURES • The DPLS1 Drain Pan Level Sensor / Control provides protection against drain pan overflow in Mitsubishi Electric M-Series, P-Series and CITY MULTI® Indoor Units. It will sense a high condensate level in the drain pan. Should this occur the control shuts down the indoor unit before an overflow can occur. Upon fault detection, the DPLS1 will produce a thermistor error code which must be resolved before the unit restarts.

Control Box

Water Sensor

Splice Connector

M2 Wire Harness

P Wire Harness

M1 Wire Harness

• Provides electronic overflow protection for Drain Pans in M-Series, P-Series and CITY MULTI® indoor units*: MFZ, MS, MSY/Z, SEZ, SLZ, PCA/PCFY, PDFY, PEA/PEAD, PKA/PKFY, PLA, PLKA/PLFY, PMFY, and PVFY. *Note: DPLS1 is not compatible with PFFY indoor units due to the construction of PFFY units drain pan. • Meets requirements as listed alternative to secondary drain pans in all indoor unit installations covered by the International Mechanical Code and adaptations ground level. • Powered by a twenty-year life Lithium battery, factory installed prior to shipment. No external electric power needed for operation. There is an audible indication of low battery condition, should it ever need to be replaced.

Type of Harness M2 Wire Harness

P Wire Harness

M1 Wire Harness

Indoor Unit Models

Connector to Indoor Unit Control Board

Connector to Thermistor

MFZ MS MSZ/Y

2 pin, female connector (with black heat shrink) to CN111

2 pin, male connector to: • RT11 (Room Temp. Thermistor)

PEA(D) PCA PKA PLA SEZ

2 pin, female connector to CN20

2 pin, male connector to: • TH1 (Room Temp. Thermistor)

PKFY-P**NBMU-E PLFY-P**NCMU-E PMFY-P**NBMU-E PVFY-P**E00A PVFY-P**E00B PVFY-P**NAMU-E SLZ PCA PEA(D) PLA PKA PCFY-P**NKMU PKFY-P**NH/KMU PLFY-P**NBMU SEZ

2 pin, male connector to: 2 pin, female connector to CN20, CN21 or CN29

4 pin, female connector to CN44

2 pin, male connector

• TH1 (Room Temp. Thermistor) or • TH22 (Pipe Temp. and Thermistor/Liquid) or • TH23 (Pipe Temp Thermistor/Gas)

• TH2 (Pipe Temp.Thermistor/Liquid) and • TH5 (Pipe Temp. Thermistor/Gas)

4 pin, male connector to: • RT12 (Coil Temp. Thermistor) 4 pin, female connector to CN112

MSZ/Y

Specifications are subject to change without notice.

2 pin, male connector

4 pin, male connector to:

MS

MFZ

Connector to Control Box

4 pin, female connector to CN113

2 pin, male connector

4 pin, male connector to: • RT12 (Coil Temp. Thermistor – Main) and • RT13 (Coil Temp. Thermistor – Sub) 4 pin, male connector to: • RT15 (Coil Temp. Thermistor) © 2015 Mitsubishi Electric US, Inc.

DIMENSIONS: DPLS1 CONTROL BOX

C

.61±.01 15.4±.1 1.71±.01 43.4±.1

.39±.01 9.8±.1

1.41±.01 35.8±.1

.79±.01 20.2±.1

1.05±.01 26.6±.1

1.40±.005 35.5±.1

.73±.01 18.4±.1

WATER SENSOR

5

9

.800±.005 20.3±.1 6

7

1.073±.005 27.2±.1

8

19 .060±.005 1.5±.1 .500±.005 12.7±.1 .125±.005 3.2±.1

.250±.005 6.4±.1

Manufactured for MITSUBISHI ELECTRIC US, INC. 1340 Satellite Boulevard. Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com

FORM# DPLS1- 201407 Specifications are subject to change without notice.

© 2015 Mitsubishi Electric US, Inc.