SUBMITTAL REVIEW 329 Innovation Boulevard, Suite 112 State College, PA 16803 814 237-2180 | www.ba-inc.com Project Name:
PSU Ag Hill Chiller Building Area 5 Shop
BA Project No.:
2016027.00
PSU Project No.:
Spec. Section/ Dwg. Ref: Title/Description:
Split System Heat Pump
Reviewer:
Amy L. Diehl
Submittal #
7
Date Received:
June 15, 2016
Resubmission Date Returned:
June 20, 2016
Review Comments: Item No.
Page No./ Drawing
Comment
1
Contractor shall provide 14kw heater or higher at the associated installed voltage.
2
Voltage changes shall be verified with Electrical Contractor.
3
Contractor to confirm unit is provided with overload protection and fan motor contactor.
APPROVED
REVISE & RESUBMIT
APPROVED AS NOTED
NOT APPROVED
SUBMIT SPECIFIED ITEM / MANUFACTURER SUBMITTAL REVIEW IS FOR CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONSTRUCTION DOCUMENTS. APPROVAL, CORRECTIONS AND/OR COMMENTS MADE AS PART OF THIS SUBMITTAL REVIEW DO NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY FROM CONFORMANCE WITH ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS, APPLICABLE CODES AND LAWS. CONTRACTOR IS RESPONSIBLE FOR DIMENSIONS, QUANTITIES, AND PERFORMANCE REQUIREMENTS TO BE CONFIRMED AND CORRELATED AT THE JOB SITE; FOR INFORMATION THAT PERTAINS SOLELY TO THE FABRICATION PROCESSES OR TO TECHNIQUES OF CONSTRUCTION; AND FOR ALL COORDINATION OF THE WORK OF ALL TRADES.
■
9:36 am, Jun 21, 2016
HLA
BY:
ALD
DATE:
06/20/16
BARTON ASSOCIATES, INC.
Barton Associates, Inc. – Consulting Engineers York | State College | Pittsburgh |1
SUBMITTAL INFORMATION PROJECT: PENN STATE UNIVERSITY AG CHILLER BUILDING OFFICE RENOVATION PSU PO #: E15-079989 SUBMITTED TO: DAREN LEWIS PENN SATE UNIVERSITY SUBMITTAL: SPLIT SYSTEM HEAT PUMP NOTES: - Contractor to verify voltage - 4 week lead time - Not included: Rigging, External Isolation, Disconnects, power or power wiring, controls not listed, spare parts, start-up or warranty service
SUBMITTED BY: MICHAEL L. DAILY KELLER EQUIPMENT SALES, INC. 100 LEADERS HEIGHTS RD., SUITE B YORK, PA 17403 717.747.5555 FAX 717.747.5566 JUNE 13, 2016 KES JOB #: 16-831
Table Of Contents Product Summary..................................................................................................................... 1 Split System Air Conditioning Units (Small) (Item A1)............................................................ 3 Tag Data.......................................................................................................................................................... 3 Product Data.................................................................................................................................................... 3 Performance Data........................................................................................................................................... 4 Mechanical Specifications .............................................................................................................................. 5 Unit Dimensions.............................................................................................................................................. 7 Weight, Clearance & Rigging Diagram........................................................................................................11 Accessory......................................................................................................................................................12
Field Installed Options - Part/Order Number Summary .........................................................13 Split System Air Conditioning Units (Small).................................................................................................13
Keller Split System
June 09, 2016
Tag Data - Split System Air Conditioning Units (Small) (Qty: 1) Item Tag(s) Qty Description Model Number A1 SSC-1 1 3 Ton Unitary Split System 4TWR4036D1000-GAM5B0B36M01S-0----000-0--0 Product Data - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1 4TWR4 Heat Pump Outdoor Unit o 3 Ton - Nominal Cooling Capacity o 200 - 230 Volt 1 Phase 60 Hertz GAM Multi-poise 4-way Air Handling Unit o Multispeed o 21.0" wide x 21.5" deep o 3 Ton air handler o Mid EFF Multi-speed Field Installed Accessories: Programmable 7 day , 3 heat/2 cool thermostat Vibration Isolators Evaporator defrost control Head pressure control Crankcase heater kit 10.80/14.40 kW Heater w/Circuit Breaker 208/240/1 Single point entry kit
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 3 of 13
Keller Split System
June 09, 2016
Performance Data - Split System Air Conditioning Units (Small) Tags SSC-1 Design clg outdoor DB (F) 95.00 Cooling EDB (F) 77.50 Cooling EWB (F) 64.50 Rated gross capacity (AHRI) (Btuh) 34000.00 Clg net total capacity (Btuh) 32525.00 Clg net sensible capacity (Btuh) 25725.00 Calc clg LDB (F) 57.40 Calc clg LWB (F) 55.30 SEER @ AHRI (btuh/watt) 14.50 Cooling airflow (cfm) 1200 Compressor power @ (specific Ambient) (W) Condenser fan power @ (specific SP) (W) Supply fan power @ (specified SP) (W)
2330.0 221.0 282.0
Htg outdoor DB (F) Heating airflow (cfm) Heating capacity @ 47F (Btuh) COP @ AHRI 47F (with Air Handler) (COP) COP @ AHRI 17F (with Air Handler) (COP) Heating capacity @ 17F (Btuh) HSPF @ AHRI (btuh/watt) Heating EDB (F) Htg system LDB (F) Htg system net capacity (Btuh)
0.00 1200 34000.00 3.60 2.50 22000.00 8.50 65.00 76.80 15330.00
Electric heat capacity @ 208 Volts (Btuh) Electric heat capacity @ 240 Volts (Btuh)
36900.00 49200.00
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 4 of 13
Keller Split System
June 09, 2016
Mechanical Specifications - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1 GAM5 Air-Tite II cabinet 2% or less air leakage Precision applied - durable door seals Specially designed air seal around refrigerant, condensate and conduit connections Double wall foamed cabinet system R-4.2 insulating value No loose fiber design Smooth cleanable interior design Sweat eliminating design Composite foamed cabinet doors Water proof cabinet design Integrated horizontal drain pans Modular cabinet with " allen wrench "quick latch" design Multi-position up/down flow horizontal left/right Side return option Control board protection pocket built into cabinet wall Alert port to view control board codes without door removal 10 alert codes Low voltage terminal connection point Quarter turn phillips head door fasteners Vortica blower with polarized plug connections and integrated slide deck for easy removal Patented enhanced coil fin Dual refrigerant compatible as shipped Slide in electric heaters with polarized plug connections (sold as accessory) UVC light kit with safety switch and polarized plug connections (sold as accessory) Labeled panels and connections Molded in 1" standard filter rail High efficiency ECM motor Soft start fan motor operation Built in fan delay modes Maximum width of 23 1/2" Compact 20 13/16" depth with doors removed Two tone color Fused 24v power Safety door switch 1-year warranty 10-year warranty registered Optional extended warranty available Vibration Isolators Neoprene-in-shear vibration isolators will be included to reduce transmission of noise and vibration to building structures, equipment and adjacent space. Head Pressure Control Accessory The Head Pressure Control accessory is a low voltage (24 Volts ) electronic head pressure control that cycles the condenser fan motor based on liquid temperature. The addition of this field installed Head Pressure Control accessory permits cooling operation to 0 deg F [-17.8 deg C] providing that non-bleed TXV's, quick start components, and compressor crankcase heat are provided with the system when required. Head Pressure Control Controls fan motor (on/off) in response to outdoor ambient temperature in conjunction with liquid line temperature. Accessory provides unit cooling operation to outdoor temperatures of 0F 4TWR4 - General The 4TWR4 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 5 of 13
Keller Split System
June 09, 2016
4TWR4 - Casing Unit casing is constructed of heavy gauge, G90 galvanized steel and painted with a weather-resistant powder paint on fan top cover and louvered panels, prepaint on all other panels. Corrosion and weatherproof CMBP-G30 base. 4TWR4 - Refrigerant Controls Refrigeration system controls include condenser fan and compressor contactor. High and low pressure controls are inherent to the compressor. A factory installed liquid line drier is standard. 4TWR4 - Compressor The compressor features internal over temperature and pressure protection and total dipped hermetic motor. Other features include: centrifugal oil pump and low vibration and noise. 4TWR4 - Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. 4TWR4 - Low Ambient Cooling As manufactured, this unit has a cooling capability to 55°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 20° F.
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 6 of 13
Keller Split System
June 09, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1
NOTES: 1. BADGE ROTATION WILL KEEP BRAND IN CORRECT POSITION. 2. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 4. GAM5 AIR HANDLERS ARE ALL TWO PIECE CABINETS. 5. SEE WEIGHT AND RIGGING PAGE FOR CONDENSATE DRAIN CONFIGURATION
21 3/4" 14 3/8"
1 1/2"
21 5/16"
5 15/16"
18 3/8"
9 3/16"
1 1/2"
3" 3/8" LIQUID LINE
7/8" GAS LINE SEE NOTE 1 CONDENSATE DRAIN 55 11/16"
1 1/2" 45 1/2"
24 13/16"
21 13/16"
17 1/8" 1 1/2"
1 1/2"
3 3/16"
18 3/8"
GAM5A0A36 AIR HANDLER UNIT DIMENSION DRAWING
1 1/2"
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 7 of 13
Keller Split System
June 09, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1
ELECTRICAL / GENERAL DATA GENERAL
(1)(2)(4)
INDOOR MOTOR
Model:
GAM5A0B36M31SA
Unit Primary Voltage: Unit Secondary Voltage: Unit Hertz: Unit Phase:
208 230 60 1
STANDARD
(5)
5.0/5.0 15.0/15.0
ELECTRIC HEAT
# of Circuit: Phase:
1 0.5 1050 1 4.1
Type: REF. Line Connections Coupling or Conn. Size - Gas: Coupling or Conn. Size - Liq.:
(3)
Type: Furnished: Number: Recommended:
Throwaway No 1 20"x20"x1"
Weights R410 Brazed 7/8" 3/8"
Net: Shipping:
142.0 lb 150.0 lb
NOTES:
230 Volt / 208 Volt Capacity Circuit #1: Capacity Circuit #2: Capacity Circuit #3:
Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
FILTERS
REFRIGERANT
230 Volt / 208 Volt Minimum Circuit Ampacity: Maximum Overload Protection:
(1)
9.60/7.20 4.80/3.60 N/A 2 1
Heater Amps Per Circuit Circuit #1: Heater Amps Per Circuit Circuit #2: Heater Amps Per Circuit Circuit #3:
40.0/34.6 20.0/17.3 N/A
Minimum Circuit Ampacity Circuit #1: Minimum Circuit Ampacity Circuit #2: Minimum Circuit Ampacity Circuit #3:
55.0/48.0 25.0/22.0 N/A
Maximum Overload Protection Circuit #1: Maximum Overload Protection Circuit #2: Maximum Overload Protection Circuit #3:
60.0/50.0 25.0/25.0 N/A
FLD = Furnished by Trane U.S. Inc. / Installed by Others
1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps (ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data. 2. 3/4" male plastic pipe (ref.: astm 1785-76) 3. Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: low velocity filter: face area (sq. ft.) = cfm / 300 high velocity filter: face area (sq. ft.) = cfm / 500 4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be installed for horizontal applications. airflow should not exceed the face value of the filter being used 5. Standard mca and mop without electric heat.
Equipment Submittal
Page 8 of 13
Keller Split System
June 09, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1
NOTES 1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED. 2. ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES. 3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
37 1/4"
SERVICE PANEL SEE NOTE 2
34 1/4"
1"
ELECTRICAL SERVICE PANEL
7/8" DIA. HOLE LOW VOLTAGE
20"
33 1/8" 1 1/8" DIA. K.O. WITH 7/8" DIA. HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWER SUPPLY
1"
8 5/8"
LIQUID LINE SERVICE VALVE, 3/8" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
6"
3 3/8"
GAS LINE 1/4" TURN BALL SERVICE VALVE, 3/4" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
3 7/8"
HEAT PUMP CONDENSER - 4TWR4030-42 DIMENSIONAL DRAWING
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 9 of 13
Keller Split System
June 09, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1
ELECTRICAL / GENERAL DATA GENERAL
POWER CONN.
Model: Unit Primary Voltage: Unit Secondary Voltage Unit Hertz: Unit Phase:
1 1 16.7 79.0
Minimum Circuit Ampacity: Maximum Circuit Breaker: Minimum Protection Rating:
1 0.20 1 0.95 -
1. Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240. 2. Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses. 3. Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0 4. * = 15, 20, 25, 30, 40 and 50 foot lineset available.
OUTDOOR MOTOR Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
COMPRESSOR 22.0 35.0 35.0
Number: Phase: Rated Load Amps: Locked Rotor Amps:
4TWR4036 208 230 60 1
NOTES:
REFRIGERANT Type: Charge: Line Size O.D. Gas: Line Size O.D. LIQ:
R-410 6.1 lb 3/4" 3/8"
C1 WEIGHT 229.0 lb 198.0 lb
DISCHARGE
SHIPPING: NET:
NOTES: C1. TOP DISCHARGE SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT C2. PLACE UNIT FROM WALL C3. PLACE SHRUBBERY AT LEAST 12" FROM UNIT ON TWO SIDES, OTHER SIDES UNRESTRICTED C4. PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT
C4
C3
C2 C3
WEIGHT AND CLEARANCE
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 10 of 13
Keller Split System
June 09, 2016
Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1
VERTICAL DOWNFLOW
REFRIGERANT CONNECTION
DOWNFLOW CONDENSATE DRAIN
REFRIGERANT CONNECTION DOWNFLOW CONDENSATE DRAIN
REFRIGERANT CONNECTION
VERTICAL UPFLOW
REFRIGERANT CONNECTION
HORIZONTAL LEFT FLOW
DOWNFLOW CONDENSATE DRAIN
HORIZONTAL RIGHT FLOW
DOWNFLOW CONDENSATE DRAIN
NOTES 1. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 2. BADGE ROTATION WILL BRAND IN CORRECT POSITION.
MINIMUM UNIT CLEARANCE TABLE TO COMBUSTIBLE MATERIALS (REQUIRED)
SERVICE CLEARANCE (RECOMMENDED)
SIDE
0
2"
FRONT BACK
0
21"
INLET DUCT
0 0
0 0
OUTLET DUCT
0
0
CLEARANCE NOTES: * 1" FOR THE FIRST 3 FT. OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALED EXCEPT MODELS BAYHTR1405, 1408, AND 1410 ARE APPROVED FOR 0" PLEMUM AND DUCT CLEARANCE IN THE UPFLOW CONFIGURATION ONLY ON TWE-P MODELS.
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 11 of 13
Keller Split System
June 09, 2016
Accessory - Split System Air Conditioning Units (Small) Item: A1 Qty: 1 Tag(s): SSC-1
6"
1 3/8"
4 5/8"
3 5/16"
3 5/16"
TCONT200 ACCESSORY - THERMOSTAT
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 12 of 13
Keller Split System
June 09, 2016
Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - Split System Air Conditioning Units (Small) Item Tag(s) Qty Description A1 SSC-1 1 3 Ton Unitary Split System
Field Installed Option Description Crankcase heater kit Vibration Isolators Programmable 7 day , 3 heat/2 cool thermostat Head pressure control Evaporator defrost control Single point entry kit 10.80/14.40 kW Htr w/Ckt Brk 208/240/1
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Model Number 4TWR4036D1000GAM5B0B36M01S -0----000-0--0 Part/Ordering Number BAYCCHT302RES BAYISLT101 TCONT802AS32DA BAYLOAM103 AY28X084 BAYSPEKT200A BAYEABC15BK1BA
Equipment Submittal
Page 13 of 13