SUBMITTAL REVIEW PROJECT NAME: GEN. CONTRACTOR: DESCRIPTION: SPEC SECTION:

NO EXCEPTIONS TAKEN PRAY CONSTRUCTION MAKE CORRECTIONS NOTED FANS REVISE & RESUBMIT 150050 REJECTED ARIC MARGOLIS ARCHITECTURE, PLLC 602 VIRGINIA ST. E. SUITE 102 CHARLESTON, WV 25301 DIGNITY HOSPICE



PHONE: 304.343.9080 EMAIL: [email protected]

Review and approval are only for conformance with the information given and the design concept of the Project as expressed in the Contract Documents. Review and approval of submittals are not conducted for the purpose of determining the accuracy and completeness of other details, such as dimensions and quantities, or for substantiating instructions for the installation or performance of equipment or systems, all of which remain the responsibility of the Contractor as required by the Contract documents. the Architect's review and approval of the Contractor's submittals shall not relieve the Contractor from any obligation contained in the Contract Documents. The Architect's review and approval shall not constitute approval of any construction means, methods, techniques, sequences, or any safety precautions or procedures. the Architects approval of specific item shall not indicate approval of an assembly of which the item is a component.

COMMENTS: FIELD COORDINATE COLORS OF ALL EXTERIOR LOUVERS AND COVERS BASED ON LOCATIONS WITH ARCHITECT.

By Aric Margolis at 9:49 am, Jul 11, 2016

Harper Engineering

PLLC

52 B Street St. Albans, WV 25177 Fax: 304.722.3603 Office: 304.722.3602

Date: July 1, 2016 Architect: Aric Margolis Architecture Project: Dignity Hospice Project #:14092 Number of copies: 1

ITEM FANS

By: Richard Standish

REMARKS X

Submittal #150500-2.0 150500 - HVAC Project: D3113 - Dignity Hospice 557 Main STreet Chapmanville, West Virginia 25508

Pray Construction Company 10331 Teays Valley Rd Scott Depot, West Virginia 25560 Phone: (304) 755-4944  Fax: (304) 755-7679

Exhaust Fans SPEC SECTION:

150500 - HVAC 

CREATED BY:

Ken Cooper(Pray Construction Company)

STATUS: 

Open

DATE CREATED:

06/30/2016 

ISSUE DATE:

06/30/2016 

REVISION:

0

RESPONSIBLE CONTRACTOR:

Clark Mechanical

RECEIVED FROM:

Brian Clark

RECEIVED DATE:   06/30/2016

SUBMIT BY: 

07/01/2016 

FINAL DUE DATE: 07/14/2016

LOCATION: 

 

TYPE:

Product Information

COST CODE: 

APPROVERS:

Katie Schultz (Pray Construction Company), Aric Margolis (Aric Margolis Architecture, PLLC)

BALL IN COURT: Aric Margolis (Aric Margolis Architecture, PLLC) DISTRIBUTION: DESCRIPTION: ATTACHMENTS: CHPMNVL HOSPICE FANS cmplt.pdf

  SUBMITTAL WORKFLOW #

NAME

SUBMITTER/ APPROVER

SENT DATE

DUE DATE



Katie Schultz

Approver 

6/30/2016

7/14/2016



Aric Margolis

Approver 

7/1/2016

7/14/2016

RETURNED RESPONSE DATE

7/1/2016

ATTACHMENTS

COMMENTS

Reviewed by Pray for Architect's Approval Pending

   

X

NO EXCEPTIONS NOTED REVIEWED EXCEPTIONS NOTED REVISE AND RESUBMIT REJECTED - RESUBMIT SUBMIT SPECIFIED ITEM

Reviewed only for general conformance with the project requirements indicated in Contract documents and for consistency with the project design concept. This review does not relieve the contractor from responsibility for errors or omissions in designs for which the contractor is responsible for all requirements of the contract documents, and for the safe and successful construction of this work. This review does not consider means, methods, techniques, sequences and operations of construction, or safety precautions or programs incidental thereto, which are the sole responsibility of the contractor.

Harper Engineering, Pllc RMS By: _________________ Date: _________________ 7-1-16 BY Pray Construction Company

DATE

COPIES TO Page 1 of 1

Printed On: 07/01/2016 01:09 PM

LOREN COOK

LOREN COOK

LOREN COOK

FANTECH

EF-2

EF-3

EF-4

EF-5

1

1

1

1

DBF4XL

GC-148

GC-148

90C17DEC

101C17DEC

MODELNO.

10

869

----

0.4

----

-------

75

---

11

869

0.4

1,614

1,705

FAN RPM

----

75

11

0.5

SP.(IN)

0.375

4,463

T.S.

3,802

480

760

CFM

62

65

WEIGHT (LBS)

---

1.5

1.5

6.9

9.5

SONES

----

34

120/1

120/ 1

120/ 1

w w 34

120/1

120/1

VOLTSI PHASE

1/6 HP

1/4 HP

HPOR WATTS

EXHAUST FAN SCHEDULE

EFͲ1ANDEFͲ2:FANSHALLRUNCONTINUOUS. EFͲ3ANDEFͲ4:FANSHALLBECONTROLLEDTHROUGHLIGHTSWITCH. EFͲ5:FANSHALLBEINTERLOCKEDWITHDRYER.

EXHAUST FAN SEQUENCE OF OPERATION

1)DIRECTDRIVEROOFEXHAUSTFANWITH24"HIGHINSULATEDROOFCURB:BIRDSCREEN;NONͲFUSEDPOWERDISCONNECT. 2)MOTORIZEDDAMPER. 3)SOLIDSTATESPEEDCONTROL(MOUNTONSIDEOFFANHOUSING). 4)DIRECTDRIVEDRYERINLINEBOOSTEREXHAUSTFANWITHPRESSURESENSOROPERATION;POWERDISCONNECT. 5)12"Wx6"HBRICKVENT 6)ROOFCAPWITHBIRDSCREENANDROOFCURB 7)DRYERVENT4"Ø,SPEEDIPRODUCTSMODELEXͲEVMLͲ04

LOREN COOK

EF-1

1

NOTES:

MANUFACTURER

MARK

QTY

DIGNITY HOSPICE AND HOME HEALTH CHAPMANVILLE, WV

1.1

1.1

5.5

20

20

20

20

(A)

(A) 5.4

MOCP

MCA

FWM

4, 7

3, 6

3, 5

1,2,3

1,2,3

NOTES

June 27, 2016

MARK: EF-1 PROJECT: DIGNITY HOSPICE & HEALTH CHAPMNVL WV DATE: june 27, 2016

ACED-EC

B D

Downblast Centrifugal Exhaust Ventilator Roof Mounted/Direct Drive Electronically Commutated Vari-Flow® Motor STANDARD CONSTRUCTION FEATURES:

All aluminum housing - Backward inclined all aluminum wheel Two piece top cap with stainless steel quick release latches (sizes 101 - 135) - Welded curb cap corners - Birdscreen Permanently lubricated ball bearing electronically commutated motor - Power rated in Input Watts - Corrosion resistant fasteners - Transit tested packaging.

C

A G T-Sq

Performance Catalog Number

Qty 1

Dimensions (inches) Flow SP Fan Input (CFM) (inwc) RPM Watts

101C17DEC

760

.500

1705

FEG

121

n/a(