Submittal #23.0 15000 - Plumbing and HVAC Project: 15-04 - U-HAUL Pompano 2150 West Sample Road Pompano Beach, Florida 33073
TGSV Enterprises, Inc. 1301 W. 68th St. Suite A Hialeah, Florida 33014 Phone: (305) 823-5755
HVAC Equipment SPEC SECTION:
15000 - Plumbing and HVAC
CREATED BY:
David Hankin(TGSV Enterprises, Inc.)
STATUS:
Open
DATE CREATED:
06/17/2016
ISSUE DATE:
06/17/2016
REVISION:
0
RESPONSIBLE CONTRACTOR:
Cool-Breeze Air Conditioning Corporation
RECEIVED FROM:
Don Gaesser
RECEIVED DATE: //
SUBMIT BY:
//
FINAL DUE DATE: 07/04/2016
LOCATION:
All Buildings
TYPE:
Specification
COST CODE:
APPROVERS:
Chris Connelly (Connelly Group Consulting Engineers)
BALL IN COURT: Chris Connelly (Connelly Group Consulting Engineers) DISTRIBUTION: Michael T. Yeary (21st Century Electrical Contractors, Inc), Pat Green (U-Haul International), Don Gaesser (Cool-Breeze Air Conditioning Corporation), Bruce McDaniel (TGSV Enterprises, Inc.), Javier Hermida (TGSV Enterprises, Inc.), Chris Connelly (Connelly Group Consulting Engineers), Thomas Averhoff (TGSV Enterprises, Inc.) DESCRIPTION: Hello Attached please find the HVAC Equipment for Bldgs. A, B, & C for your review and Approval. Thank you ATTACHMENTS:
SUBMITTAL WORKFLOW # 1
NAME Chris Connelly
SUBMITTER/ APPROVER
SENT DATE
Approver
DUE DATE 7/4/2016
RETURNED RESPONSE DATE
ATTACHMENTS
COMMENTS
Pending
TGSV Enterprises, Inc.
REVIEWED FOR SUBMISSION DATE: 6/20/2016 Checked By
BY
TGSV Enterprises, Inc.
T.A.
DATE
COPIES TO
Page 1 of 1
Printed On: 06/20/2016 10:52 AM
SUBMITTALS For:
EQUIPMENT PROJECT: U‐HAUL POMPANO
General Contractor: TGSV ENTERPRISES
13120 SW 130 TERRACE MIAMI, FL 33186 PH (305)226-2665 FAX (305)253-4420 Licensed & Insured CACO 24325 www.Cool-Breezeac.com
Submittal
Prepared For:
Date: May 20, 2016
Sold To: Cool Breeze AC
Job Name: U-Haul Project Pompano
Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 11 Split System Air Conditioning Units (Small)
The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.
Renny Urdaneta Trane 2884 Corporate Way Miramar, FL 33025 Phone: (305) 592-0672 Fax: (305) 592-0221
J:\JOBS\297\115107\5\U-Haul Project Pompano Submittals_2016-05-20.doc
Table Of Contents Product Summary..................................................................................................................... 1 Split System Air Conditioning Units (Small) (Items A1 - A3) .................................................. 3 Tag Data .................................................................................................................................................. 3 Product Data ............................................................................................................................................ 3 Mechanical Specifications........................................................................................................................ 4 Unit Dimensions ....................................................................................................................................... 8 Weight, Clearance & Rigging Diagram................................................................................................... 20 Accessory .............................................................................................................................................. 22 Field Wiring ............................................................................................................................................ 23
U-Haul Project Pompano
May 20, 2016
Tag Data - Split System Air Conditioning Units (Small) (Qty: 11) Item Tag(s) Qty Description A1 AHU/ASHP-7, AHU/ASHP-8, 3 5 Ton Unitary Split Systems AHU/ASHP-9 A2 AHU/ASHP-3, AHU/ASHP-4, 4 4 Ton Unitary Split Systems AHU/ASHP-5, AHU/ASHP-6 A3 AHU/CU-1, AHU/CU-2, 4 5 Ton Unitary Split Systems AHU/CU-3, AHU/CU-4
Model Number 4TWA3060B4000-TAM4A00000-1S 4TWA3048B4000-TAM4A00000-1S 4TTA3060D4000-TEM3A0000S-1S
Product Data - Split System Air Conditioning Units (Small) All Condensing Units’ Coils to be provided with Luvata anti corrosion coating Item: A1 Qty: 3 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9 4TWA3 Heat Pump Outdoor Unit 5 Ton - Nominal Cooling Capacity 460 Volt 3 Phase 60 Hertz CU 208 Volt 1 Phase 60 Hertz AHU Multi-poise 4-way AHU 5 Ton air handler Programmable 7 day , 3 heat/2 cool thermostat (Fld) Item: A2 Qty: 4 Tag(s): AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6 4TWA3 Heat Pump Outdoor Unit 4 Ton - Nominal Cooling Capacity 460 Volt 3 Phase 60 Hertz CU 208 Volt 1 Phase 60 Hertz AHU Multi-poise 4-way AHU 4 Ton air handler Programmable 7 day , 3 heat/2 cool thermostat (Fld) Item: A3 Qty: 4 Tag(s): AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4 Cooling Only Outdoor Unit 5 Ton - Nominal Cooling Capacity 460 Volt 3 Phase 60 Hertz CU 208 Volt 1 Phase 60 Hertz AHU Multi-poise 4-way AHU 5 Ton air handler Programmable 7 day , 3 heat/2 cool thermostat (Fld)
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 3 of 23
U-Haul Project Pompano
May 20, 2016
Mechanical Specifications - Split System Air Conditioning Units (Small) Item: A1 - A3 Qty: 11 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9, AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6, AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4 4TTA3 - General This unit is fully charged from the factory for matched indoor section and up to 180" of piping. Unit is designed to operate at outdoor ambient temperatures as high as 115.0 F]. Cooling capacities matched with a wide selection of air handlers and furnace coils that are A.R.I certified. The unit shall be UL listed. Exterior must be designed for outdoor application. 4TTA3 - Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Corrosion and weatherproof CMBP-G30 Duratuff base. 4TTA3 - Compressor The Climatuff compressor features internal over temperature and pressure protector, total dipped hermetic motor. Other features include: centrifugal oil pump, and low vibration and noise. 4TTA3 - Condenser Coil The Spine Fin coil is continuously wrapped, corrosion resistant, all aluminum with minimum brazed joints. The coil is 3/8" O.D. seamless aluminum glued to a continuous aluminum fin. Coils are lab tested to withstand 2000.0 lb of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. 4TTA3 - Refrigerant controls Refrigeration system controls include condenser fan and compressor contactor. High and low pressure protection is inherent to the compressor. Another standard feature is the factory installed liquid line drier. 4TWA3 Heat Pump General Unit Shall be fully charged from the factory for matched indoor section and up to 180" of piping. This unit must be designed to operate at outdoor ambient temperatures as high as 115.0 F. Cooling capacities shall be matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit shall be UL listed. Exterior must be designed for outdoor application. 4TWA3 Heat Pump Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Corrosion and weatherproof CMBP-G30 DuraTuff base. 4TWA3 Heat Pump Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. 4TWA3 Heat Pump Compressor The Climatuff compressor features internal over temperature and pressure protector and total dipped hermetic motor. Other features include: centrifugal oil pump, and low vibration and noise. 4TWA3 Heat Pump Low Ambient Cooling As manufactured, this unit has a cooling capability to 55.0 F. The addition of an evaporator defrost control permits operation to 40.0 F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30.0 F. 4TWA3 Heat Pump Refrigerant Controls Refrigeration system controls include condenser fan and compressor contactor. High and low pressure controls are inherent to the compressor. Another standard feature is the liquid line dryer. TAM4 Air-Tite IITM Cabinet Double Wall Foamed and Formed Cabinet System Water Proof Cabinet Design R-4.2 Insulating Value Composite Foamed Cabinet Doors Sweat Eliminating Cabinet Design Loose Fiber Eliminating Cabinet Design Smooth Cleanable Cabinet Design 2% or Less air leakage FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 4 of 23
U-Haul Project Pompano
May 20, 2016
Precision Durable Door Seals Quarter Turn Phillips Head Door Fasteners 5/16" Allen Wrench "Quick Latch" Modular Cabinet Multi-Position UP/Down Flow Horizontal Left /Right Side Return Option Braze in Refrigerant Connection Primary/Secondary Condensate Connections Conduit Connection with Easy Removal Plugs Alert Port to view Codes without door removal Vortica Blower with Integrated Slide Deck for Easy Removal Polarized Plug connections on Blower Control Protection Pocket Aluminum Coil with Integrated Slide Deck for Easy Removal Polarized Plug connections on Coil EEV Slide in Electric Heaters Polarized Plug connections for Electric Heater Labeled Panels and connections 1 1/4" to 1" and 1 3/4" to 1/2" Conduit connection on Left, Right and Top Molded in 1"Standard Filter rail Electronic Expansion Valve (EEV) With Low Dual Refrigerant Compatible as Shipped Low Voltage Terminal Connection Point 8 Alert Codes Enhanced Coil Fin Patented Blow Through Design PSC 3 Speed Motor Maximum Width of 24 1/2" Compact 20 13/16"depth with doors removed Integrated Horizontal Drain pans Single Color Fused 24V Power Safety Door Switch 1 Year Warranty 10 Year Warranty Registered Warranty Mirrors Outdoor Optional extended warranty available TEM3 Painted metal cabinet with captured foil face insulation 2% or less air leakage R-4.2 Insulating Value Multi-Position UP/Down Flow, Horizontal Left /Right ALL Aluminum Coil with Enhanced Patented Coil Fin Electric Heaters with polarized plug connections (sold as accessory) R-410A Thermal Expansion Valve Low Voltage Pigtail Connections Draw Through Design Horizontal Drain pan Single Color Fused 24V Power
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 5 of 23
U-Haul Project Pompano
FLD = Furnished by Trane U.S. Inc. / Installed by Others
May 20, 2016
Equipment Submittal
Page 6 of 23
U-Haul Project Pompano
FLD = Furnished by Trane U.S. Inc. / Installed by Others
May 20, 2016
Equipment Submittal
Page 7 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 3 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9
NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
21 13/16" 1 1/2" 1 1/2"
23 1/2"
14 3/8"
5 15/16"
20 1/2"
1 1/2"
LIQUID LINE 3/8" GAS LINE 7/8"
10 5/16"
3"
61 11/16" 51 1/2" 1 1/2"
21 13/16"
1 1/2"
17 1/8"
27"
3 1/8"
1 1/2"
20 1/2"
1 1/2"
AIRHANDLER - TAM4A0A60 DRAWING
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 8 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 3 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9
ELECTRICAL / GENERAL DATA GENERAL
(1)(2)(4)
INDOOR MOTOR
Model:
TAM4A0C60S51SA
Unit Primary Voltage: Unit Secondary Voltage: Unit Hertz: Unit Phase:
208 230 60 1
STANDARD
(5)
10.0/10.0 15.0/15.0
ELECTRIC HEAT
# of Circuit: Phase:
Type: REF. Line Connections Coupling or Conn. Size - Gas: Coupling or Conn. Size - Liq.:
(3)
1 1.0 1050 1 7.6 -
Type: Furnished: Number: Recommended:
R-410A
Shipping: Net:
Throwaway No 1 22"x20"x1"
Weights 171.0 lb 159.0 lb
7/8" 3/8"
NOTES:
240 Volt / 208 Volt Capacity Circuit #1: Capacity Circuit #2: Capacity Circuit #3:
Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
FILTERS
REFRIGERANT
230 Volt / 208 Volt Minimum Circuit Ampacity: Maximum Overload Protection:
(1)
N/A N/A N/A N/A N/A
Heater Amps Per Circuit Circuit #1: Heater Amps Per Circuit Circuit #2: Heater Amps Per Circuit Circuit #3:
N/A N/A N/A
Minimum Circuit Ampacity Circuit #1: Minimum Circuit Ampacity Circuit #2: Minimum Circuit Ampacity Circuit #3:
N/A N/A N/A
Maximum Overload Protection Circuit #1: Maximum Overload Protection Circuit #2: Maximum Overload Protection Circuit #3:
N/A N/A N/A
FLD = Furnished by Trane U.S. Inc. / Installed by Others
1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps (ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data. 2. 3/4" male plastic pipe (ref.: astm 1785-76) 3. Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: low velocity filter: face area (sq. ft.) = cfm / 300 high velocity filter: face area (sq. ft.) = cfm / 500 4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be installed for horizontal applications. airflow should not exceed the face value of the filter being used 5. Standard mca and mop without electric heat.
Equipment Submittal
Page 9 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 3 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9
37 1/4"
UNIT DIMENSTIONS
SERVICE PANEL SEE NOTE 2
34 1/4"
DIM - D
7/8"
DIM - E
3/8"
NOTES 1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED. 2. ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES.
1"
ELECTRICAL SERVICE PANEL
7/8" DIA. HOLE LOW VOLTAGE
20"
41 1/8" 1 1/8" DIA. K.O. WITH 7/8" DIA. HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWER SUPPLY
1"
8 5/8"
LIQUID LINE SERVICE VALVE, "E" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
LIQUID LINE SERVICE VALVE, "E" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
8 5/8"
6"
3 3/8" 3 7/8"
FLD = Furnished by Trane U.S. Inc. / Installed by Others
GAS LINE 1/4" TURN BALL SERVICE VALVE, "D" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
Equipment Submittal
6"
3 3/8" 3 7/8" GAS LINE SERVICE VALVE, "D" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
Page 10 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A1 Qty: 3 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9
ELECTRICAL / GENERAL DATA GENERAL
POWER CONN.
Model: Operating Voltage: Unit Primary Voltage: Unit Secondary Voltage Unit Hertz: Unit Phase:
1 3 7.8 52.0
Minimum Circuit Ampacity: Maximum Circuit Breaker: Minimum Protection Rating:
1 0.20 825 3 0.86 -
1. Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240. 2. Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses. 3. Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0 4. * = 15, 20, 25, 30, 40 and 50 foot lineset available.
OUTDOOR MOTOR Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
COMPRESSOR 10.0 15.0 15.0
Number: Phase: Rated Load Amps: Locked Rotor Amps:
4TWA3060 414-506 460 60 3
NOTES:
REFRIGERANT Type: Charge: Line Size O.D. Gas: Line Size O.D. LIQ:
R-410 9.7 lb 7/8" 3/8"
C1 WEIGHT 244.0 lb 280.0 lb
DISCHARGE
NET SHIPPING
NOTES: C1. TOP DISCHARGE SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT C2. PLACE UNIT FROM WALL C3. PLACE SHRUBBERY AT LEAST 12" FROM UNIT ON TWO SIDES, OTHER SIDES UNRESTRICTED C4. PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT
C4
C3
C2 C3
WEIGHT AND CLEARANCE
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 11 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A2 Qty: 4 Tag(s): AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6
NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 21 13/16" 1 1/2"
14 3/8"
5 15/16"
1 1/2"
23 1/2"
20 1/2"
1 1/2"
LIQUID LINE 3/8"
GAS LINE 7/8" 10 5/16"
3"
56 7/8" 46 11/16" 1 1/2"
21 13/16"
1 1/2"
17 1/8"
24 1/2"
3 1/8"
1 1/2"
20 1/2"
1 1/2"
AIRHANDLER - TAM4A0A48 DRAWING
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 12 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A2 Qty: 4 Tag(s): AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6
ELECTRICAL / GENERAL DATA GENERAL
(1)(2)(4)
INDOOR MOTOR
Model:
TAM4A0C48S41SA
Unit Primary Voltage: Unit Secondary Voltage: Unit Hertz: Unit Phase:
208 230 60 1
STANDARD
(5)
4.0/4.0 15.0/15.0
ELECTRIC HEAT
# of Circuit: Phase:
Type: REF. Line Connections Coupling or Conn. Size - Gas: Coupling or Conn. Size - Liq.:
(3)
1 0.50 1075 1 3.1 5.5
Type: Furnished: Number: Recommended:
R-410A
Shipping: Net:
Throwaway No 1 22"x20"x1"
Weights 155.0 lb 143.0 lb
7/8" 3/8"
NOTES:
240 Volt / 208 Volt Capacity Circuit #1: Capacity Circuit #2: Capacity Circuit #3:
Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
FILTERS
REFRIGERANT
230 Volt / 208 Volt Minimum Circuit Ampacity: Maximum Overload Protection:
(1)
N/A N/A N/A N/A N/A
Heater Amps Per Circuit Circuit #1: Heater Amps Per Circuit Circuit #2: Heater Amps Per Circuit Circuit #3:
N/A N/A N/A
Minimum Circuit Ampacity Circuit #1: Minimum Circuit Ampacity Circuit #2: Minimum Circuit Ampacity Circuit #3:
N/A N/A N/A
Maximum Overload Protection Circuit #1: Maximum Overload Protection Circuit #2: Maximum Overload Protection Circuit #3:
N/A N/A N/A
FLD = Furnished by Trane U.S. Inc. / Installed by Others
1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps (ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data. 2. 3/4" male plastic pipe (ref.: astm 1785-76) 3. Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: low velocity filter: face area (sq. ft.) = cfm / 300 high velocity filter: face area (sq. ft.) = cfm / 500 4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be installed for horizontal applications. airflow should not exceed the face value of the filter being used 5. Standard mca and mop without electric heat.
Equipment Submittal
Page 13 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A2 Qty: 4 Tag(s): AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6
37 1/4"
UNIT DIMENSTIONS
SERVICE PANEL SEE NOTE 2
34 1/4"
DIM - D
7/8"
DIM - E
3/8"
NOTES 1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED. 2. ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES.
1"
ELECTRICAL SERVICE PANEL
7/8" DIA. HOLE LOW VOLTAGE
20"
41 1/8" 1 1/8" DIA. K.O. WITH 7/8" DIA. HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWER SUPPLY
1"
8 5/8"
LIQUID LINE SERVICE VALVE, "E" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
LIQUID LINE SERVICE VALVE, "E" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
8 5/8"
6"
3 3/8" 3 7/8"
FLD = Furnished by Trane U.S. Inc. / Installed by Others
GAS LINE 1/4" TURN BALL SERVICE VALVE, "D" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
Equipment Submittal
6"
3 3/8" 3 7/8" GAS LINE SERVICE VALVE, "D" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
Page 14 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A2 Qty: 4 Tag(s): AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6
ELECTRICAL / GENERAL DATA GENERAL
POWER CONN.
Model: Operating Voltage: Unit Primary Voltage: Unit Secondary Voltage Unit Hertz: Unit Phase:
1 3 7.1 46.0
Minimum Circuit Ampacity: Maximum Circuit Breaker: Minimum Protection Rating:
1 0.20 825 3 0.6 -
1. Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240. 2. Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses. 3. Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0 4. * = 15, 20, 25, 30, 40 and 50 foot lineset available.
OUTDOOR MOTOR Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
COMPRESSOR 8.0 15.0 15.0
Number: Phase: Rated Load Amps: Locked Rotor Amps:
4TWA3048 414-506 460 60 3
NOTES:
REFRIGERANT Type: Charge: Line Size O.D. Gas: Line Size O.D. LIQ:
R-410 8.1 lb 7/8" 3/8"
C1 WEIGHT 241" 277.0 lb
DISCHARGE
NET SHIPPING
NOTES: C1. TOP DISCHARGE SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT C2. PLACE UNIT FROM WALL C3. PLACE SHRUBBERY AT LEAST 12" FROM UNIT ON TWO SIDES, OTHER SIDES UNRESTRICTED C4. PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT
C4
C3
C2 C3
WEIGHT AND CLEARANCE
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 15 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A3 Qty: 4 Tag(s): AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4
5 13/16" 21 1/16" 2 1/8" 1"
12 1/8"
7 7/8"
GAS LINE 7/8"
1"
LIQUID LINE 3/8"
2.00
23 1/2"
21 1/2"
24 13/16" 19 3/8" 21 13/16"
5"
2 9/16"
3 5/16"
1"
1 7/16" 2"
7"
1 9/16"
1.38
9 11/16"
VERTICAL DOWNFLOW CONNECTIONS
2 1/16" 2 3/4"
2 1/16"
5 1/4"
0.88
6 15/16"
2.00 1.38 1.50 TYP
2 1/8"
B
51 1/4"
GAS LINE 7/8" 24 9/16"
B
6 3/4"
4 5/16"
7/8"
18 3/4"
1 7/16"
7"
1 5/16" 1 1/16"
9 11/16"
LIQUID LINE 3/8"
3/8" 7/8"
NOTES: 1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
21 3/4"
7/8" 7/8"
AIRHANDLER DRAWING
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 16 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A3 Qty: 4 Tag(s): AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4
ELECTRICAL / GENERAL DATA GENERAL
(1)(2)(4)
INDOOR MOTOR
Model:
TEM3A0C60S21SA
Unit Primary Voltage: Unit Secondary Voltage: Unit Hertz: Unit Phase:
208 230 60 1
STANDARD
(5)
8.0/8.0 15.0/15.0
ELECTRIC HEAT
# of Circuit: Phase:
Type: REF. Line Connections Coupling or Conn. Size - Gas: Coupling or Conn. Size - Liq.:
(3)
1 0.50 1050 1 7.6 -
Type: Furnished: Number: Recommended:
R-410A
Shipping: Net:
Throwaway No 1 16"x20"x1"
Weights 180.0 lb 170"
7/8" 3/8"
NOTES:
240 Volt / 208 Volt Capacity Circuit #1: Capacity Circuit #2: Capacity Circuit #3:
Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
FILTERS
REFRIGERANT
230 Volt / 208 Volt Minimum Circuit Ampacity: Maximum Overload Protection:
(1)
N/A N/A N/A N/A N/A
Heater Amps Per Circuit Circuit #1: Heater Amps Per Circuit Circuit #2: Heater Amps Per Circuit Circuit #3:
N/A N/A N/A
Minimum Circuit Ampacity Circuit #1: Minimum Circuit Ampacity Circuit #2: Minimum Circuit Ampacity Circuit #3:
N/A N/A N/A
Maximum Overload Protection Circuit #1: Maximum Overload Protection Circuit #2: Maximum Overload Protection Circuit #3:
N/A N/A N/A
FLD = Furnished by Trane U.S. Inc. / Installed by Others
1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps (ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data. 2. 3/4" male plastic pipe (ref.: astm 1785-76) 3. Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: low velocity filter: face area (sq. ft.) = cfm / 300 high velocity filter: face area (sq. ft.) = cfm / 500 4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be installed for horizontal applications. airflow should not exceed the face value of the filter being used 5. Standard mca and mop without electric heat.
Equipment Submittal
Page 17 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A3 Qty: 4 Tag(s): AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4
37 1/4"
NOTES 1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED. 2. ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES.
SERVICE PANEL SEE NOTE 2
34 1/4"
1"
ELECTRICAL SERVICE PANEL
7/8" DIA. HOLE LOW VOLTAGE
20"
37 1/4" 1 1/8" DIA. K.O. WITH 7/8" DIA. HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWER SUPPLY
1"
8 5/8"
LIQUID LINE SERVICE VALVE, 3/8" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
LIQUID LINE SERVICE VALVE, "E" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
8 5/8"
6"
3 3/8" 3 7/8"
FLD = Furnished by Trane U.S. Inc. / Installed by Others
GAS LINE 1/4" TURN BALL SERVICE VALVE, 7/8" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
Equipment Submittal
6"
3 3/8" 3 7/8" GAS LINE SERVICE VALVE, "D" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING.
Page 18 of 23
U-Haul Project Pompano
May 20, 2016
Unit Dimensions - Split System Air Conditioning Units (Small) Item: A3 Qty: 4 Tag(s): AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4
ELECTRICAL / GENERAL DATA GENERAL
POWER CONN.
Model: Operating Voltage: Unit Primary Voltage: Unit Secondary Voltage Unit Hertz: Unit Phase:
1 3 7.8 52.0
Minimum Circuit Ampacity: Maximum Circuit Breaker: Minimum Protection Rating:
1 0.20 825 3 0.60 -
1. Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240. 2. Calculated in accordance with N.E.C. Use only HACR circuit breakers or fuses. 3. Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0 4. * = 15, 20, 25, 30, 40 and 50 foot lineset available.
OUTDOOR MOTOR Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps:
COMPRESSOR 10.0 15.0 15.0
Number: Phase: Rated Load Amps: Locked Rotor Amps:
4TTA3060* 414-506 460 60 3
NOTES:
REFRIGERANT Type: Charge: Line Size O.D. Gas: Line Size O.D. LIQ:
R-410 8.0 lb 7/8" 3/8"
C1 WEIGHT 226.0 lb 261.0 lb
DISCHARGE
NET SHIPPING
NOTES: C1. TOP DISCHARGE SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT C2. PLACE UNIT FROM WALL C3. PLACE SHRUBBERY AT LEAST 12" FROM UNIT ON TWO SIDES, OTHER SIDES UNRESTRICTED C4. PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT
C4
C3
C2 C3
WEIGHT AND CLEARANCE
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 19 of 23
U-Haul Project Pompano
May 20, 2016
Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small) Item: A1, A2 Qty: 7 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9, AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6
VERTICAL DOWNFLOW
REFRIGERANT CONNECTION
DOWNFLOW CONDENSATE DRAIN
REFRIGERANT CONNECTION DOWNFLOW CONDENSATE DRAIN
REFRIGERANT CONNECTION
VERTICAL UPFLOW
REFRIGERANT CONNECTION
HORIZONTAL LEFT FLOW
DOWNFLOW CONDENSATE DRAIN
HORIZONTAL RIGHT FLOW
DOWNFLOW CONDENSATE DRAIN
NOTES 1. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 2. BADGE ROTATION WILL BRAND IN CORRECT POSITION.
MINIMUM UNIT CLEARANCE TABLE TO COMBUSTIBLE MATERIALS (REQUIRED) SIDE FRONT BACK INLET DUCT OUTLET DUCT
SERVICE CLEARANCE (RECOMMENDED)
0 0 0 0 0
2" 21" 0 0 0
CLEARANCE NOTES: * 1" FOR THE FIRST 3 FT. OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALED EXCEPT MODELS BAYHTR1405, 1408, AND 1410 ARE APPROVED FOR 0" PLEMUM AND DUCT CLEARANCE IN THE UPFLOW CONFIGURATION ONLY ON TWE-P MODELS.
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 20 of 23
U-Haul Project Pompano
May 20, 2016
Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small) Item: A3 Qty: 4 Tag(s): AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4
REFRIGERANT CONNECTION
DOWNFLOW CONDENSATE DRAIN
REFRIGERANT CONNECTION
UPFLOW CONDENSATE DRAIN
VERTICAL UPFLOW
VERTICAL DOWNFLOW
REFRIGERANT CONNECTION
HORIZONTAL CONDENSATE DRAIN
HORIZONTAL CONDENSATE DRAIN HORIZONTAL LEFT FLOW
HORIZONTAL RIGHT FLOW
MINIMUM UNIT CLEARANCE TABLE TO COMBUSTIBLE MATERIALS (REQUIRED)
NOTES 1. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 2. BADGE ROTATION WILL BRAND IN CORRECT POSITION.
SIDE FRONT BACK INLET DUCT OUTLET DUCT
0 0 0 0 1"
SERVICE CLEARANCE (RECOMMENDED) 2" 21" 0 1" 0
CLEARANCE NOTES: * 1" FOR THE FIRST 36". OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALED 0" AFTER THE FIRST
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 21 of 23
U-Haul Project Pompano
May 20, 2016
Accessory - Split System Air Conditioning Units (Small) Item: A1 - A3 Qty: 11 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9, AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6, AHU/CU-1, AHU/CU-2, AHU/CU-3, AHU/CU-4
6"
1 3/8"
4 5/8"
3 5/16"
3 5/16"
TCONT200 ACCESSORY - THERMOSTAT
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 22 of 23
U-Haul Project Pompano
May 20, 2016
Field Wiring - Split System Air Conditioning Units (Small) Item: A1, A2 Qty: 7 Tag(s): AHU/ASHP-7, AHU/ASHP-8, AHU/ASHP-9, AHU/ASHP-3, AHU/ASHP-4, AHU/ASHP-5, AHU/ASHP-6
SINGLE SPEED OUTDOOR SECTION
R
R
O
O
Y
Y
T
G T
24 VAC REVERSING VALVE COMPRESSOR O.D. SENSOR BR/X2 or BK
W1
24 VAC COMMON
W2
TO "FAULT" ON T'STAT
W3 B
TYPICAL AIR HANDLER LOW VOLTAGE TERMINAL BOARD TO POWER SUPPLY PER LOCAL CODES INTER-COMPONENT WIRING 24 VOLT
FACTORY WIRING
LINE VOLT 24 VOLT
FIELD WIRING
LINE VOLT
NOTES: 1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES 2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE 3. LOW VOLTAGE WIRING TO BE 18 A.W.G. MINIMUM CONDUCTOR 4. USE COPPER CONDUCTORS ONLY 5. TERMINALS W2 AND W3 WILL HAVE INTERNAL CONNECTIONS ONLY IF 2nd AND 3rd CONTACTORS ARE USED BY THE HEATER FOR CONTROLLING THE POWER TO ELECTRIC HEATING ELEMENTS. IF 2nd AND 3rd (BH AND CH) CONTACTORS ARE NOT USED, THEN FIELD CONNECTIONS W2 AND W3 CAN BE OMITTED AS APPROPRIATE. 6. IF ODT IS NOT USED, THEN CONNECT APPROPRIATE JUMPERS FROM W1 TO W2 AND W3 ON LVTB
FLD = Furnished by Trane U.S. Inc. / Installed by Others
Equipment Submittal
Page 23 of 23