Submittal #220000-4.0 220000 - Plumbing
Project: 1523 - Mathworks LSMP 19 Superior Drive Natick, Massachusetts 01760
SD - UG Floor Drains and Cleanouts [2.5, 2.6] APPROVERS:
David Brown (Consigli Construction Co., Inc) Mathworks LSMP Gensler Team (Gensler)
CREATED BY:
David Brown(Consigli Construction Co., Inc)
RESPONSIBLE CONTRACTOR:
North Shore Mechanical Dennis Robarge (North Shore Mechanical)
STATUS:
Open
TYPE:
Material Delivery
SPEC SECTION:
220000 - Plumbing
COPIES TO: Ben Trendell (Gensler), Patrick Murphy (RDK Engineers), RDK Boston Submittals (RDK Engineers), Kayla Beane (RDK Engineers) , David Brown (Consigli Construction Co., Inc) DESCRIPTION: ATTACHMENTS:
ARCHITECT'S STAMP
CONTRACTOR'S STAMP
SUBMITTAL REVIEW NO EXCEPTIONS TAKEN. MAKE CORRECTIONS AS NOTED. Resubmittal not required unless Contractor cannot comply with corrections noted. REVISE AS NOTED AND RESUBMIT. RESUBMIT PROPERLY. Submittal not reviewed for reasons noted. NOT REVIEWED. Submittal not required by Contract Documents. RECEIVED FOR CLIENT’S RECORD ONLY. Submittal not reviewed.
NICKEL BRONZE FINISH IS ACCEPTABLE BT, GENSLER, 05/17/2016
Contractor is responsible for checking for deviations between this Submittal and differing information or conditions in the Contract Documents and field conditions; for determining or substantiating the accuracy and completeness of other details such as dimensions and quantities; for substantiating instructions for installation or performance of equipment or systems designed by Contractor; for construction means, methods, techniques, schedules, sequences, procedures, and fabrication processes; for errors and omissions in Submittals; for coordination of the Work of the trades, safety precautions and performing the Work in a safe and satisfactory manner and in conformance with the Contract Documents.
v1 3/2012
Date:
Tue May 17, 2016
Project No: 11.6652.000 Submittal:
Revise & Resubmit Rejected
Spec. Section: 220000
Submittal No.: 220000-4
Date: 4/22/2016
By: David Brown
If so marked, approval is given for design only. It does not relieve the subcontractor from complying with the requirements of the contract, contract drawings and specifications. The subcontractor shall be responsible for all dimensions, quantities, schedules and field conditions.
If more than one submittal review stamp appears on this Submittal, the most stringent action and notations thereon apply. Signature of a submittal review stamp by Gensler or a consultant does not imply that it has reviewed work not within its professional discipline or scope of services.
Ben Trendell
X Approved for A/E Review Approved as Noted for A/E Review
Gensler has reviewed this Submittal, but only for the purpose of checking for conformance with the design intent expressed in the Contract Documents. Gensler’s action on a specific item does not indicate approval of an assembly of which the item is a component, nor of an item as delivered and installed if it does not conform to the Contract Documents.
By:
Consigli Construction Co., Inc.
(SDR-P02) 2016-04-25T21_54_40_9226214-0477d2ed
//gensler.ad/Projects/11/11.6652.000/Documentation/6 - Const Admin/6S - Submittals/DIV
SUBMITTAL WORKFLOW
# 1
NAME Dennis Robarge
SUBMITTER/ APPROVER
SENT DATE
DUE DATE
Submitter
4/4/2016
4/29/2016
2
David Brown
Approver
4/25/2016
4/29/2016
3
Mathworks LSMP Gensler Team
Approver
4/25/2016
5/13/2016
BY
Page 1 of 1
RETURNED RESPONSE DATE 4/22/2016
4/25/2016
DATE
266 Summer Street Boston, Massachusetts 02210
ATTACHMENTS
COMMENTS
Submitted
Approved
220000-4 Revision 0 SD - UG Floor Drains and Cleanouts [2.5, 2.6].pdf
Pending
COPIES TO
Printed On:04/25/2016 05:54PM
FD-340-Y-SET
Tag:
FD-1 Floor Drain
Area Drain with 12" Round Fixed Top, Grate Supported by Bucket
SPECIFICATION: Watts Drainage Products FD-340-Y-SET epoxy coated cast iron area drain with anchor flange, membrane clamp with weepholes, 12-1/2"(318) diameter fixed top, loose set heel proof ductile iron grate supported by bucket, and no hub connection (standard).
12-1/2" (318)
Pipe Sizing (Select One) Suffix
11-7/8" (302)
Description 2"(51) Pipe Size 3"(76) Pipe Size 4"(102) Pipe Size 5"(127) Pipe Size (NH only) 6"(152) Pipe Size 8"(203) Pipe Size (NH only)
2 3 4 5 6 8
2-7/8" (73)
Outlet Type (Select One) Suffix NH P T X
Description No Hub (MJ) Push On Threaded Outlet Inside Caulk
✔
Options (Select One or More) Suffix
6-1/4" (159)
PIPE SIZE
-1 -6 -7 -8 -13 -34 -F4-50 -F4-1 -F6-1 -G-50 -G-1 -SO -US
Description Nickel Bronze Top Vandal Proof Trap Primer Tapping Backwater Valve (3"/4" Only) Galvanized Closure Plug 4" Round Cast Iron Funnel
✔
4" Round Nickel Bronze Funnel 6" Round Nickel Bronze Funnel 4x9" Oval Cast Iron Funnel 4x9" Oval Nickel Bronze Funnel Side Outlet (2,3,4 only) Buy American Compliant
Optional Body Material Suffix -60 -61
Load Rating & Free Area Load Rating
Free Area Sq. In.
*HD
16
Description PVC Body w/Socket Outlet ABS Body w/Socket Outlet
* The load classifications are in accordance with the American National Standards ASME A112.21.1M ASME Ratings are as follows: HD - Safe Live Load 7500-10000 lbs.(3375-4500kg) The above categories are given as a guide only. Please consult factory.
Mathworks-LSMP (UG) 19 Superior Drive Natick, MA
ES-WD-FD-340-Y-SET USA 1348
FD-340-Y-SET
FD-100-M
Tag:
Floor Drain with Square Strainer
FCO Floor Cleanout
SPECIFICATION: Watts Drainage FD-100-M epoxy coated cast iron floor drain with anchor flange, reversible clamping collar with primary & secondary weepholes, adjustable square heel proof nickel bronze strainer, and no hub (standard) outlet.
Components
8-1/8" (206)
B3
B3-XYC
M
FC-1
STRAINER SIZE Pipe Sizing (Select One)
MAX
Suffix
Description
2 3 4 6
2"(51) Pipe Size 3"(76) Pipe Size 4"(102) Pipe Size 6"(152) No Hub Only
MAX
✔
Outlet Type (Select One) Suffix
CHART B
NH P T X
Description No Hub (MJ) Push On Threaded Outlet Inside Caulk
✔
Strainer (Select One) Suffix M5 M6 M8
Description 5"x5" Nickel Bronze 6"x6" Nickel Bronze 8"x8" Nickel Bronze
✔
Options (Select One or More) Suffix
PIPE SIZE
Strainer Size Str. Dia.
Max.
Min.
5"x5"(127x127) 7/8"(22) 3-1/4"(83) 6"x6"(152x152) 1"(25) 3-1/4"(83) 8"x8"(203x203) 1-3/8"(35) 3-5/8"(92)
Load Rating
Free Area Sq. In.
*MD *MD *MD
9 12 26
* The load classifications are in accordance with the American National Standards ASME A112.21.1M ASME Ratings are as follows: MD - Safe Live Load 2000-4999 lbs.(900-2250kg) The above categories are given as a guide only. Please consult factory.
Chart B Std.
P
Pipe Size
No Hub
Push On
2"(51) 3"(76) 4"(102) 6"(152)
3-5/8"(92) 3-5/8"(92) 3-5/8"(92) 3-1/2"(89)
4-1/4"(108) 4-1/4"(108) 4-1/4"(108)
T X 60/61 Inside Female PVC/ Thread Caulk ABS 4-1/4"(108) 4-1/2"(114) 4"(102) 4-1/4"(108) 4-1/2"(114) 4"(102) 4-1/4"(108) 4-1/2"(114) 4"(102)
-9 Hinged grate option for 6"x6"(152x152) or 8"x8"(203x203) strainer only
Description
-5 -6
Sediment Bucket Vandal Proof
-7 -8 -9 -13
Trap Primer Tapping Backwater Valve (2",3", 4" Only) Hinged Grate (For 6", 8" Strainer Only) Galvanized Body
-15
Strainer Extension (DD-50)
✔
-F4-50 4" Round Cast Iron Funnel -F4-1 4" Round Nickel Bronze Funnel -F6-1 6" Round Nickel Bronze Funnel -G-50 4x9" Oval Cast Iron Funnel -G-1 -SO -US
4x9" Oval Nickel Bronze Funnel Side Outlet Buy American Compliant
Optional Body Material Suffix -60 -61
Description PVC Body w/Socket Outlet ABS Body w/Socket Outlet
Mathworks-LSMP (UG)
19 Superior Drive Natick, MA
ES-WD-FD-100-M USA 1343
FD-100-M
CO-200-R Tag:
FD-2 Floor Drain
Floor Cleanout with Round Top
SPECIFICATION: Watts Drainage CO-200-R epoxy coated cast iron floor cleanout with 5” (127) round adjustable gasketed nickel bronze top, removable gas tight gasketed brass cleanout plug, and no hub (standard) outlet. Components 7" (178) 5-1/8" (130)
B4-34
R
34B
Pipe Sizing (Select One) Suffix
MAX. 2-1/2" (64) MIN. 3/4" (19)
Description 2"(51) Pipe Size 3"(76) Pipe Size 4"(102) Pipe Size
2 3 4
Outlet Type (Select One) Suffix NH P X
Description No Hub (MJ) Push On Inside Caulk
✔
Options (Select One or More)
Chart A
Suffix
Description
-C -6 -13 -CF -US
Membrane Clamp Vandal Proof Galvanized Body Carpet Cleaning Flange Buy American Compliant
✔
Optional Body Material Suffix
Description
-60 -61
PVC Body w/Poly Plug ABS Body w/Poly Plug
PIPE SIZE
Chart A Pipe Size 2" 3" 4"
NH(MJ)
P
60/61
No Hub
Push On
PVC/ ABS
4-1/2" (114) 4-1/2" (114) 4-3/4" (121)
5-1/2" (140) 5-1/2" (140) 5-1/2" (140)
4" (102) 4" (102) 4" (102)
Load Rating *MD
* The load classifications are in accordance with the American National Standards ASME A112.21.1M ASME Ratings are as follows: MD - Safe Live Load 2000-4999 lbs.(900-2250kg) The above categories are given as a guide only. Please consult factory.
Mathworks-LSMP (UG)
19 Superior Drive Natick, MA
ES-WD-CO-200-R USA 1304
CO-200-R